Knowledgebase Quick Starts
Using the Data Logging Utility Software to recover data
The Data Logging utility is the only supported method for
retrieving data, that has been stored in the processor.
1.
Install the DLOG utility (found at
2.
Execute
DLCA1764.EXE
3.
Configure
Port, Baud Rate
, and
DF1 Node
as shown below.
4.
Click “Connect”.
FYI - By default the MicroLogix 1100 communications are
configured for 19200 baud If using defaults select 19200 above,
otherwise select the baud rate configured in the MicroLogix Channel
Configuration Screen.
If a correct configuration has been selected the utility software will
indicate that it has connected to the processor as shown below.
ATTENTION
!
If any other software package, such as RSLINX has
control of the computers communication port or if the
wrong COM port is selected or a processor other then
the MicroLogix 1100 is connected to the computer you
will not be able to continue.