Publication 1763-RM001C-EN-P - October 2009
24
I/O Configuration
I/O Addressing
Addressing Details
The I/O addressing scheme and examples are shown below.
(1) I/O located on the controller (embedded I/O) is slot 0.
I/O added to the controller (expansion I/O) begins with slot 1.
Addressing Examples
Xd:s.w/b
File Type
Input (I) or Output (O)
Data File Number
Slot Number
(1)
Word
Bit
Bit Delimiter
Word Delimiter
Slot Delimiter
Format
Explanation
Od:s.w/b
Id:s.w/b
X
File Type
Input (I) or Output (O)
d
Data File Number
(optional)
0 = output, 1 = input
:
Slot delimiter
(optional, not required for Data Files 2 to 255)
s
Slot number (decimal)
Embedded I/O: slot 0
Expansion I/O:
•
slots 1 to 4 for MicroLogix 1100 (See page 15 for an illustration.)
.
Word delimiter. Required only if a word number is necessary as noted below.
w
Word number
Required to read/write words, or if the discrete bit number is above 15.
Range: 0 to 255
/
Bit delimiter
b
Bit number
0 to 15
Addressing Level
Example Address
(1)
Slot
Word
Bit
Bit Addressing
O:0/4
(2)
Output Slot 0 (Embedded I/O)
word 0
output bit 4
O:2/7
Output Slot 2 (Expansion I/O)
word 0
output bit 7
I:1/4
Input Slot 1 (Expansion I/O)
word 0
input bit 4
I:0/15
Input Slot 0 (Embedded I/O)
word 0
input bit 15
Word Addressing
O:1.0
Output Slot 1 (Expansion I/O)
word 0
I:7.3
Input Slot 7 (Expansion I/O)
word 3
I:3.1
Input Slot 3 (Expansion I/O)
word 1
(1) The optional Data File Number is not shown in these examples.
(2) A word delimiter and number are not shown. Therefore, the address refers to word 0.