Rockwell Automation Publication 1734-UM013C-EN-P - August 2010
71
Configure the Module in a GuardLogix Controller
Chapter
6
9.
In the Revision boxes, enter the appropriate major and minor revision of
the 1734-AENT adapter.
10.
From the Electronic Keying pull-down menu, choose the appropriate
keying method for the 1734-AENT adapter.
11.
From the Connection pull-down menu, choose the appropriate
connection for the 1734-AENT adapter.
12.
From the Chassis Size pull-down menu, enter the number of POINT I/O
modules that will be attached to the 1734-AENT adapter plus 1 for the
1734-AENT adapter.
IMPORTANT
1734-AENT adapter firmware must be major revision 3
or later to support POINT Guard I/O modules.
Choose
Description
Exact Match
Module and type series must exactly match or the module
will be rejected by the controller.
Compatible Module
Controller will check module type and revision for
compatibility. Compatible modules that match or are
newer will be accepted.
Disable Keying
Controller will check module type, but will accept any
version.
Do not choose Disable Keying.
Choose
Description
Listen Only
Read or verify standard digital I/O data only, but does not
control the modules. (When you have multiple controllers,
one controller is used to control and the other controllers
are used to monitor.)
None
The adapter makes a direct connection to each of the
module’s listed under the 1734-AENT adapter in the I/O
Configuration tree.
Rack Optimization
Standard digital I/O data is collected into a single rack
image.
This does not include specialty, analog, or
POINT Guard I/O modules.
TIP
If there are no standard digital I/O modules in your
POINT I/O system, choose None.
IMPORTANT
Do not count terminal bases. Enter only the number of
physical modules installed, plus 1 for the adapter.
This number must match exactly. You cannot enter a
higher number anticipating future expansion.