Safety Functions
Chapter
2
Safety Inputs
Read this section for information about safety inputs and their associated test
outputs. A safety input can optionally be used with test outputs. Safety inputs are
used to monitor safety input devices.
Using a Test Output with a Safety Input
A test output can be used in combination with a safety input for short circuit,
cross-channel, and open-circuit fault detection. Configure the test output as a
pulse test source and associate it to a specific safety input.
Figure 4 - Example Use of a POINT Guard I/O Input Module
Figure 5 - Test Pulse in a Cycle
For the 1734-IB8S module, the pulse width (X) is typically 525 μs; the pulse
period (Y) is typically 144 ms.
TIP
The test output can also be configured as a power supply to
source 24V DC to an external device, for example, a light
curtain.