Rockwell Automation Publication 1608S-UM001C-EN-P - November 2018
19
Chapter
4
Operation, Maintenance, and Troubleshooting
The left-side cover can be removed to access the communication ports.
User Controls and
Indicators
These user controls and indicators are available:
• The i-Sense® Management Console (requires an Ethernet connection
to monitor)
• The
www.igrid.com
website (available from any web browser)
• Red and Green status indicators (see
Table 6
and
Table 7
below)
• RESET push button (located inside left cover)
• Heartbeat
♡
push button (located inside left cover)
Status Indicators
The status indicators will flash to indicate status; the flash codes are listed in the
tables below. Additional status information is available by connecting to the
i-Sense Management Console via the Ethernet port.
Startup/Confirmation Blink:
At power-up and to confirm a push-button
operation, both status indicators will blink rapidly for a few seconds.
Table 6 -
Green NORMAL Status Indicator
Flash Codes
Flash
Rate
Meaning
Off
No Power
1
OK
2
Voltage events captured, waiting to transmit
3
Voltage deviation event detected, voltage has not yet returned to normal (PQ event in progress)
4
Establishing connection to the i-Grid servers
5
Connected to the i-Grid servers, uploading PQ event data
Constant
Not operating properly. Push RESET button