38
Rockwell Automation Publication 1500-UM055I-EN-P - December 2021
Chapter 2 Installation – Arc-Resistant Enclosure
Figure 32 - Contactor Bus Bars (Trailer Fuse Block for Clip-on Fuses Shown)
9. Disconnect the secondary control wiring from the control power
transformer (CPT) and remove the CPT mounting plate. Leave the CPT
attached to the plate.
10. To access the right side of the power bus, remove the 1/4-20 self-tapping
screws (12 lb•ft [15N•m]) from the lower glass-polyester bus access cover
and remove the cover (see
11. Reverse the procedure to reassemble the cabinet. Ensure that the barriers
are put back in place.
Figure 33 - Access to Right Side of Power Bus
Contactor Bus Bars
Mounting Bolts
Trailer Fuse Block
ATTENTION:
The CPT is heavy and assistance may be required
to safely remove and transport the unit. Use caution when
removing the CPT. Failure to do so may result in personal injury
and/or damage to the equipment.
Remove self-
tapping screws
Summary of Contents for 1512B
Page 6: ...6 Rockwell Automation Publication 1500 UM055I EN P December 2021 Notes...
Page 74: ...74 Rockwell Automation Publication 1500 UM055I EN P December 2021 Chapter 4 Maintenance Notes...