34
Rockwell Automation Publication 1500-UM055I-EN-P - December 2021
Chapter 2 Installation – Arc-Resistant Enclosure
Rear Access
1. Remove the hardware
securing the center rear bus access cover (see
).
2. Remove the center rear bus access cover.
3. Once the rear bus cover is removed you will see the three power bus bars
and ground bus (see
).
Figure 25 - Access to Power Bus from Side and Rear of Cabinet
Side Access
A side bus access cover is located on each side of the controller.
1. Remove the hardware from the appropriate side bus access cover.
2. Remove the side bus access cover (see
3. ArcShield units at the end of a line-up have a ground connection to the
inner plate of the side bus access cover (see
). This
connection must be maintained to ensure unit arc resistant
performance.
Figure 26 - Side Bus Access Cover Warning Label
Side Bus Access Cover
Center Rear Bus Access Cover