Appendix D Integrated Protective Maintenance Grounding Device
Key Interlocking
An optional mechanical key interlock is available to lock the IPMG device in the
CLOSE or OPEN positions. Contact the factory for further details.
Auxiliary Switches
The IPMG device comes standard with either 2-Form C auxiliary contacts or
with an optional 4-Form C auxiliary contact configuration. These auxiliary
contacts indicate the mechanical and electrical position of the IPMG device.
OPEN (ungrounded load connections) or CLOSED (grounded load
connections). These auxiliary switches can be incorporated into the
controller's control circuit. Their electrical ratings are shown
Figure 99 - 400 A IPMG showing Auxiliary Contact
Table 4 - Auxiliary Switch Specifications
Description
Value
Rated voltage (V AC/V DC)
250
Maximum continuous current (A)
10
Contact configuration
DPDT
Contacts available (standard)
2-Form C
Contacts available (optional)
4-Form C
Breaking capacity >5000 electrical
operations
(1)
(A)
(1) When time constant is < 40 ms.
110/120V AC
10
220/240V AC
10
125V DC
0.3
250V DC
0.15
UL code
L59
Mechanical life (operations)
3,000,000