Rockwell Automation Publication 1500-UM055I-EN-P - December 2021
25
Chapter 1 Installation – Standard Enclosure
Figure 17 - Access to Load Cable Conduit Openings (Top exit cable configuration shown)
(LV panels removed for clarity)
3. Remove the appropriate load cable conduit openings in the top or bottom
of the cabinet (see
Top Exiting Load Cables
4. Load cables for the bottom power cell should be routed first. Pull the
cables into the cabinet through the appropriate opening (see
).
Run the cables behind the current transformer mounting plate and into
the bottom power cell.
Remove Cable Duct Boot to
access Load Cable Conduit
opening for cables exiting
from bottom Power Cell
Current Transformer
Mounting Plate
Connect Load Cables to
Current Transformers
Refer to Dimensional Drawings provided with order
documentation for additional details.