background image

14

15

Outdoor Unit Installation

Outdoor Unit Installation

NOTE:

 

The minimum distance between the 

outdoor unit and walls described in the 
installation guide does not apply to airtight 
rooms. Be sure to keep the unit unobstructed 
in at least two of the three directions (M, N, P) 
(See Fig. 5.4)  

 

Fig. 5.4

Outdoor Unit Mounting Dimensions

Fig. 5.5

L

H

300 cm / 118” or more

A

60 cm / 23.6” 

    or more

150 cm / 59” 

    or more

25 cm / 9.8” 

  or more

25 cm / 9.8” 

   or more

Rows of series installation

L < H

L < 1/2H

L

A

25 cm / 9.8” or more

1/2H < L < H

30 cm / 11.8” or more

L > H

Can not be installed

               The relations between H, A and L 
                         are as follows.

B

A

D

The mounting dimensions vary among different outdoor units.
The fixing bolt head diameter should be more than 12mm.

Outdoor Unit Dimentsion (mm)

Mounting Dimentsion (mm)

W

H

D

A

B

952

1333

415

634

404

900

1170

350

590

378

Fig. 5.3

M

N

P

30 cm / 12” from back wall

 

  
 

60 cm / 24” above

30 cm / 12” on left

30 cm / 12” on right

200 cm / 79” in front

W

H

Drain Joint Installation

NOTE:

 Make sure the water drains to a safe 

location where it will not cause water 
damage or a slipping hazard.  

Seal

Drain joint

(A)

(B)

Base pan hole of 

outdoor unit

Seal 

Fig. 5.5

Notes On Drilling Hole In Wall

You must drill a hole in the wall for the  
refrigerant piping, and the signal cable that will 
connect the indoor and outdoor units.  

1. 

 

Determine the location of the wall hole 
based on the location of the outdoor unit.  

2. 

 

Using a 65-mm (2.5”) core drill, drill a hole 
in the wall.  

NOTE:

 When drilling the wall hole,  

make sure to avoid wires, plumbing, 
and other sensitive components. 

3. 

 

Place the protective wall cuff in the hole. 
This protects the edges of the hole and will 

help seal it when you finish the installation 

process.  

If the drain joint comes with a rubber seal

(see Fig. 5.5 - A), do the following:

1. Fit the rubber seal on the end of the drain joint 

that will connect to the outdoor unit.

2. Insert the drain joint into the hole in the base 

pan of the unit.

3. Rotate the drain joint 90° until it clicks in place 

facing the front of the unit.

4. Connect a drain hose extension (not included) 

to the drain joint to redirect water from the 

unit during heating mode.

If the drain joint doesn’t come with a rubber 

seal (see Fig. 5.5 - B ), do the following: 

 

1. Insert the drain joint into the hole in the base 

pan of the unit. The drain joint will click in 

place.

2. Connect a drain hose extension (not included) 

to the drain joint to redirect water from the 

unit during heating mode.

_

_

_

Summary of Contents for FHA-H54R410INV9

Page 1: ...FHA H54R410INV9 FHA H70R410INV9 FHA H54R410INV9 FHA H70R410INV9 Installation Manual Floor Standing Type AIR CONDITIONERS...

Page 2: ...ipe Installation 16 Table of Contents Table of Contents Installation Manual Indoor Unit Installation 09 Installation Overview 08 1 2 5 3 4 6 Refrigerant Piping Connection 17 A Refrigerant Piping Conne...

Page 3: ...y combustible materials Do not install the unit in a location that may be exposed to combustible gas leaks If combustible gas accumulates around the unit it may cause re Do not operate your air condit...

Page 4: ...checked for leaks proper record keeping of all checks is strongly recommended Accessories The air conditioning system comes with the following accessories Use all of the installation parts and access...

Page 5: ...25 Indoor Unit Parts Fig 4 1 1 7 8 9 10 2 3 4 5 6 Indoor Unit Installation Air outlet Operation panel Horizontal air ow control louver Vertical air ow control louver Air inlet 2 sides Drain pipe vent...

Page 6: ...tape and any components screw bolt xing hole Air inlet Grid 2 Open the two boxes for storing the remote control found on either side of the indoor unit then undo the screws on the operation panel 3 U...

Page 7: ...le position on back side Pipe wire hole position on the bottom Refrigerant drain Pipe hole Refrigerant drain Pipe hole First remove the metal Then attach the ratproof board into the hole ratproof boar...

Page 8: ...oor unit Seal Fig 5 5 Notes On Drilling Hole In Wall You must drill a hole in the wall for the refrigerant piping and the signal cable that will connect the indoor and outdoor units 1 Determine the lo...

Page 9: ...9 above the ground If it touches the ground the unit may become blocked and malfunction If you discharge the water directly into a sewer make sure that the drain has a U or S pipe to catch odors that...

Page 10: ...the torque values in table 7 1 NOTE Use both a spanner and a torque wrench when connecting or disconnecting pipes to from the unit Pipe gauge Tightening torque Flare dimension A Unit mm Inch Flare sha...

Page 11: ...n the product Outdoor Unit Wiring Before performing any electrical or wiring work turn off the main power to the system 1 Prepare the cable for connection a You must rst choose the right cable size be...

Page 12: ...e wrench in a 1 4 counterclockwise turn Listen for gas to exit the system then close the valve after 5 seconds Flare nut Cap Valve body Valve stem Fig 9 2 9 Watch the Pressure Gauge for one minute to...

Page 13: ...ndoor unit work properly e Ensure the manual buttons on the indoor unit works properly f Check to see that the drainage system is unimpeded and draining smoothly g Ensure there is no vibration or abno...

Page 14: ...25 24 1 2 3 4 2 000 5 6...

Page 15: ...4 1 6 35 8 3 9 52 60 x 0 64 30 x 0 32 15 x 0 16 R22 65 x 0 69 30 x 0 32 x 0 16 15 R410A 23 22 Flare shape 76 1 9 2 9 0 1 40 0 1 0 1 1 2 3 4 5 15 1x105 76 6 5 7 8 1 4 5 9 10 12 7 5 164 5 25 2 1 12 7...

Page 16: ...Flare shape 3 0 118 PCB T5A 250VAC T3 15A 250VAC 1 H07RN F 8 1 7 18 13 7 16 18 13 14 25 18 12 30 25 10 _ 6 0 75 10 6 1 16 10 1 5 25 16 2 5 32 35 4 45 32 6 _ 5 9 15 U 2 8 1 U 3 U 4 5 6 8 1 1 5 9 15 U...

Page 17: ...6 4 R0 4 0 8 45 2 90 4 A 9 5 12 7 15 9 19 1 22 23 2 0 91 26 4 1 04 8 4 0 33 13 2 0 52 16 2 0 64 19 2 0 76 23 7 0 93 26 9 1 06 8 7 0 34 13 5 0 53 16 5 0 65 19 7 0 78 20 18 36 35 367 357 47 45 480 459 6...

Page 18: ...90 1 7 1 10 17 16 3 7 3 9 3 2 0 5 0 4 0 2 1 6 7 1 2 7 1 2 26 3 9 0 03 4 5 65 6 2 5 0 4 1 6 2 7 1 9 5 S U 1 2 90 1 2...

Page 19: ...404 900 1170 350 590 378 W H 3 5 5 5 5 6 M N P L H L 1 2H L A 1 2H L H L H L A H 9 8 25 11 8 30 L H 300 cm 118 or more A 60 cm 23 6 or more 150 cm 59 or more 25 cm 9 8 or more 25 cm 9 8 or more 5 5 5...

Page 20: ...1 5 2 5 13 12 2 4 6 3 1 2 3 4 57 4 67 67 4 5 8 4 9 4 1 5 2 5 3 5 1 2 3 60cm 23 6 M1 Fig 4 6...

Page 21: ...10 11 Fig 4 4 Air inlet Grid 11 8 30 78 7 200 2 5 19 7 50 19 7 50 4 2 24 8 629 17 9 455 76 2 1935 18 0 456 4 3 1 2 3 4 5 6 4 4 1 2 1 2 1 M8 2 4 5 3 4 5 1...

Page 22: ...9 8 L N 1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 5 6 7 8 9 10 MC MC 10 14 17 18 21 23 25 4 1...

Page 23: ...7 6 2 2 1 2 1 2 1 1 1 1 1 1 1 2 1 1 1 1 1 2 1 2 3 50 5 4 24 5 25 3 9 ST3 9 12 ST 2 9 10 AAA...

Page 24: ...5 4 1 2 3 4 NEC 5 6 8 7 8 9 10 IEC 11 12 3 13 10 30 RCD 14 15 16 17 18 19 20 21 22 23 24 3 1 1 2...

Page 25: ...3 2 04 09 10 07 13 13 14 15 16 09 08 1 2 5 3 4 6 17 17 19 20 20 21 7 8 L N 22 22 23 9 10 24 25 11 MC MC...

Reviews: