12
13
Fig. 4.9
4. Use adhesive vinyl tape to begin binding the
piping together. Start binding the tape at the
bottom end of the drainage hose, and make
sure that the connectors are secured tightly.
Step 7: Applying the sealant putty and
installing the wall hole cover
1. Tidy up the already bound piping.
2. Evenly apply the sealant putty to the gaps
between the piping and the wall, then press
on the putty firmly.
3. Pull the wall hole cover apart to open it.
After fastening tightly to the piping, push it
into the hole in the wall to securely fasten it
to the wall and complete the installation.
1.
Lay the connecting piping flat on the ground.
Place the drainage hose, refrigerant pipe, and
all electrical wiring (making sure that both
ends are arranged correctly) next to the
piping.
2. Using the drainage hose as a guide, measure
and adjust the length of the low voltage
wiring, high voltage wiring, any other
electrical wiring, and refrigerant pipe. Use
cable ties to initially fasten them in place.
3. Arrange the piping so that the drainage hose
is on the bottom, the connecting piping is in
the middle, and the electrical wiring is at the
top.
Step 6. Piping and binding
Fig. 4.8
Fig. 4.7
drainage
electrical wiring
refrigerant pipe
The electrical wiring, drainage hose, and
refrigerant pipe must exit the binding in a
suitable place. All binding must be mutually
connected, evenly applied, and aesthetically
pleasing.
NOTE
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Only models with a ventilation function
contain ventilation ducting.
•
The amount and type of electrical wiring
used may vary according to the specific
model.
•
The ends of the ventilation ducting and
electrical wiring are different, please check
carefully before starting to bind.
Fig. 4.6
2.
Insert the ratproof board into the unit and
hold it in place tightly.
3.
Use a knife to cut a small hole by following the
markings on the ratproof board.
(See Fig. 4.6)
Pipe/wire-hole positions on both sides
Refrigerant/drain
Pipe hole
�
�
67
�
67
57.4
Pipe/wire-hole position on back side
Pipe/wire-hole position on the bottom
Refrigerant/drain
Pipe hole
Refrigerant/drain
Pipe hole
First remove the metal
Then attach the ratproof
board into the hole
ratproof board
Markings
CAUTION
Outdoor Unit Installation
Outdoor Unit Installation Instructions
Step 1: Select installation location.
The outdoor unit should be installed in the
location that meets the following requirements:
Place the outdoor unit as close to the indoor
unit as possible.
Ensure that there is enough room for
installation and maintenance.
The air inlet and outlet must not be
obstructed or exposed to strong wind.
Ensure the location of the unit will not be
subject to snowdrifts, accumulation of leaves
or other seasonal debris. If possible, provide
an awning for the unit. Ensure the awning
does not obstruct airflo
w.
The installation area must be dry and well
ventilated.
There must be enough room to install the
connecting pipes and cables and to access
them for maintenance.
The area must be free of combustible
gases and chemicals.
The pipe length between the outdoor and
indoor unit may not exceed the maximum
allowable pipe length.
If possible, DO NOT install the unit
where it is exposed to direct sunlight.
If possible, make sure the unit is located
far away from your neighbors’ property
so that the noise from the unit will not
disturb them.
If the location is exposed to strong winds
(for example: near a seaside), the unit
must be placed against the wall to
shelter it from the wind. If necessary,
use an awning.
(See Fig. 5.1 & 5.2)
Install the indoor and outdoor units,
cables and wires at least 1 meter from
televisions or radios to prevent static or
image distortion. Depending on the radio
waves, a 1 meter distance may not be
enough to eliminate all interference.
Strong wind
Strong wind
Strong wind
Fig. 5.1
Fig. 5.2
Step 2: Install outdoor unit.
Fix the outdoor unit with anchor bolts (M10)
>60cm / 23.6”
Fix with bolts
•
Be sure to remove any obstacles
that may block air circulation.
•
Make sure you refer to Length
Specifications to ensu
re there is
enough room for installation and
maintenance.
Fig. 5.3
CAUTION
Indoor Unit Installation Instruction
Summary of Contents for FHA-H54R410INV9
Page 14: ...25 24 1 2 3 4 2 000 5 6...
Page 20: ...1 5 2 5 13 12 2 4 6 3 1 2 3 4 57 4 67 67 4 5 8 4 9 4 1 5 2 5 3 5 1 2 3 60cm 23 6 M1 Fig 4 6...
Page 22: ...9 8 L N 1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 5 6 7 8 9 10 MC MC 10 14 17 18 21 23 25 4 1...
Page 23: ...7 6 2 2 1 2 1 2 1 1 1 1 1 1 1 2 1 1 1 1 1 2 1 2 3 50 5 4 24 5 25 3 9 ST3 9 12 ST 2 9 10 AAA...