background image

Users in European Countries may be required to properly dispose of this unit. This appliance contains 
refrigerant and other potentially hazardous materials. When disposing of this appliance, the law 
requires special collection and treatment. 

DO NOT

 dispose of this product as household waste or 

unsorted municipal waste. 

24

25

Test Run

European Disposal Guidelines

 

Before Test Run

A test run must be performed after the entire 

system has been completely installed. Confirm 

the following points before performing the test: 
   a)

 

The indoor and outdoor units are properly 
installed.

b)

 

Piping and wiring are properly connected.

c)

 

Ensure that there are no obstacles near the 
inlet and outlet of the unit that might cause 
poor performance or product malfunction.   

d)

 

The refrigeration system does not leak. 

e)  The drainage system is unimpeded and 

draining to a safe location. 

f)  The heating insulation is properly installed.
g)

 

The grounding wires are properly connected.

h)

 

The length of the piping and the added 
refrigerant stow capacity have been 
recorded. 

i)

 

The power voltage is the correct voltage 
for the air conditioner. 

Failure to perform the test run may result in 
unit damage, property damage or personal injury. 

Test Run Instructions

1.

 

Open both the liquid and gas stop valves. 

2.

 

Turn on the main power switch and allow the 
unit to warm up.  

3.

 

Set the air conditioner to COOL mode.

4.

 

For the Indoor Unit
a.  Ensure the remote control and its buttons 

work properly.  

b.

 

Ensure the louvers move properly and can 
be changed using the remote control. 

c.

 

Double check to see if the room 
temperature is being registered correctly. 

d.

 

Ensure the indicators on the remote 
control and the display panel on the indoor 
unit work properly. 

e.

 

Ensure the manual buttons on the indoor 
unit works properly. 

f.

 

Check to see that the drainage system is 
unimpeded and draining smoothly. 

g.  Ensure there is no vibration or abnormal 

noise during operation. 

5.

 

For the Outdoor Unit
a.

 

Check to see if the refrigeration system is 
leaking. 

b.

 

Make sure there is no vibration or 
abnormal noise during operation. 

c.

 

Ensure the wind, noise, and water 
generated by the unit do not disturb your 
neighbors or pose a safety hazard.

6.

 

Drainage Test
a.

 

Ensur

e the drainpipe flows smoothl

y. New 

buildings should perform this test before 

finishing the ceiling. 

b.

 

Remove the test cover. Add 2,000ml of 
water to the tank through the attached 
tube. 

c.

 

Turn on the main power switch and run 
the air conditioner in COOL mode.  

d.

 

Listen to the sound of the drain pump to 
see if it makes any unusual noises.  

e.

 

Check to see that the water is discharged. 
It may take up to one minute before the 
unit begins to drain depending on the 
drainpipe.  

f.

 

Make sure that there are no leaks in any of 
the piping. 

g.

 

Stop the air conditioner. Turn off the main 
power switch and reinstall the test cover.  

NOTE:

 If the unit malfunctions or does not 

operate according to your expectations, 
please refer to the Troubleshooting section 
of the Owner’s Manual before calling 
customer service.  

 CAUTION

 

When disposing of this appliance, you have the following options:

• 

Dispose of the appliance at designated municipal electronic waste collection facility.

• 

When buying a new appliance, the retailer will take back the old appliance free of charge.

• 

The manufacturer will also take back the old appliance free of charge.

• 

Sell the appliance to certified scrap metal dealers.

NOTE:

 Disposing of this appliance in the forest or other natural surroundings endangers your 

health and is bad for the environment. Hazardous substances may leak into the ground water 

and enter the food chain.

Summary of Contents for FHA-H54R410INV9

Page 1: ...FHA H54R410INV9 FHA H70R410INV9 FHA H54R410INV9 FHA H70R410INV9 Installation Manual Floor Standing Type AIR CONDITIONERS...

Page 2: ...ipe Installation 16 Table of Contents Table of Contents Installation Manual Indoor Unit Installation 09 Installation Overview 08 1 2 5 3 4 6 Refrigerant Piping Connection 17 A Refrigerant Piping Conne...

Page 3: ...y combustible materials Do not install the unit in a location that may be exposed to combustible gas leaks If combustible gas accumulates around the unit it may cause re Do not operate your air condit...

Page 4: ...checked for leaks proper record keeping of all checks is strongly recommended Accessories The air conditioning system comes with the following accessories Use all of the installation parts and access...

Page 5: ...25 Indoor Unit Parts Fig 4 1 1 7 8 9 10 2 3 4 5 6 Indoor Unit Installation Air outlet Operation panel Horizontal air ow control louver Vertical air ow control louver Air inlet 2 sides Drain pipe vent...

Page 6: ...tape and any components screw bolt xing hole Air inlet Grid 2 Open the two boxes for storing the remote control found on either side of the indoor unit then undo the screws on the operation panel 3 U...

Page 7: ...le position on back side Pipe wire hole position on the bottom Refrigerant drain Pipe hole Refrigerant drain Pipe hole First remove the metal Then attach the ratproof board into the hole ratproof boar...

Page 8: ...oor unit Seal Fig 5 5 Notes On Drilling Hole In Wall You must drill a hole in the wall for the refrigerant piping and the signal cable that will connect the indoor and outdoor units 1 Determine the lo...

Page 9: ...9 above the ground If it touches the ground the unit may become blocked and malfunction If you discharge the water directly into a sewer make sure that the drain has a U or S pipe to catch odors that...

Page 10: ...the torque values in table 7 1 NOTE Use both a spanner and a torque wrench when connecting or disconnecting pipes to from the unit Pipe gauge Tightening torque Flare dimension A Unit mm Inch Flare sha...

Page 11: ...n the product Outdoor Unit Wiring Before performing any electrical or wiring work turn off the main power to the system 1 Prepare the cable for connection a You must rst choose the right cable size be...

Page 12: ...e wrench in a 1 4 counterclockwise turn Listen for gas to exit the system then close the valve after 5 seconds Flare nut Cap Valve body Valve stem Fig 9 2 9 Watch the Pressure Gauge for one minute to...

Page 13: ...ndoor unit work properly e Ensure the manual buttons on the indoor unit works properly f Check to see that the drainage system is unimpeded and draining smoothly g Ensure there is no vibration or abno...

Page 14: ...25 24 1 2 3 4 2 000 5 6...

Page 15: ...4 1 6 35 8 3 9 52 60 x 0 64 30 x 0 32 15 x 0 16 R22 65 x 0 69 30 x 0 32 x 0 16 15 R410A 23 22 Flare shape 76 1 9 2 9 0 1 40 0 1 0 1 1 2 3 4 5 15 1x105 76 6 5 7 8 1 4 5 9 10 12 7 5 164 5 25 2 1 12 7...

Page 16: ...Flare shape 3 0 118 PCB T5A 250VAC T3 15A 250VAC 1 H07RN F 8 1 7 18 13 7 16 18 13 14 25 18 12 30 25 10 _ 6 0 75 10 6 1 16 10 1 5 25 16 2 5 32 35 4 45 32 6 _ 5 9 15 U 2 8 1 U 3 U 4 5 6 8 1 1 5 9 15 U...

Page 17: ...6 4 R0 4 0 8 45 2 90 4 A 9 5 12 7 15 9 19 1 22 23 2 0 91 26 4 1 04 8 4 0 33 13 2 0 52 16 2 0 64 19 2 0 76 23 7 0 93 26 9 1 06 8 7 0 34 13 5 0 53 16 5 0 65 19 7 0 78 20 18 36 35 367 357 47 45 480 459 6...

Page 18: ...90 1 7 1 10 17 16 3 7 3 9 3 2 0 5 0 4 0 2 1 6 7 1 2 7 1 2 26 3 9 0 03 4 5 65 6 2 5 0 4 1 6 2 7 1 9 5 S U 1 2 90 1 2...

Page 19: ...404 900 1170 350 590 378 W H 3 5 5 5 5 6 M N P L H L 1 2H L A 1 2H L H L H L A H 9 8 25 11 8 30 L H 300 cm 118 or more A 60 cm 23 6 or more 150 cm 59 or more 25 cm 9 8 or more 25 cm 9 8 or more 5 5 5...

Page 20: ...1 5 2 5 13 12 2 4 6 3 1 2 3 4 57 4 67 67 4 5 8 4 9 4 1 5 2 5 3 5 1 2 3 60cm 23 6 M1 Fig 4 6...

Page 21: ...10 11 Fig 4 4 Air inlet Grid 11 8 30 78 7 200 2 5 19 7 50 19 7 50 4 2 24 8 629 17 9 455 76 2 1935 18 0 456 4 3 1 2 3 4 5 6 4 4 1 2 1 2 1 M8 2 4 5 3 4 5 1...

Page 22: ...9 8 L N 1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 5 6 7 8 9 10 MC MC 10 14 17 18 21 23 25 4 1...

Page 23: ...7 6 2 2 1 2 1 2 1 1 1 1 1 1 1 2 1 1 1 1 1 2 1 2 3 50 5 4 24 5 25 3 9 ST3 9 12 ST 2 9 10 AAA...

Page 24: ...5 4 1 2 3 4 NEC 5 6 8 7 8 9 10 IEC 11 12 3 13 10 30 RCD 14 15 16 17 18 19 20 21 22 23 24 3 1 1 2...

Page 25: ...3 2 04 09 10 07 13 13 14 15 16 09 08 1 2 5 3 4 6 17 17 19 20 20 21 7 8 L N 22 22 23 9 10 24 25 11 MC MC...

Reviews: