ELECTRICAL SPECIFICATIONS
Single phase wiring
Z25 (25 kg/hr nominal)***
Voltage L1 to Neutral [V]
100 120 208 220 240 277
Power [kW] *
2.2
2.2
3.0
3.0
3.0
3.0
Current at rated capacity [A] *
22.3 18.6 14.3 13.5 12.4 10.7
Breaker - D/J type [A] (125%) *
30
25
20
20
15
15
Z40 (40kg/hr nominal)***
Voltage L1 to Neutral [V]
100 120 208 220 240 277
Power [kW] *
3.6
3.6
4.8
4.8
4.8
4.8
Current at rated capacity [A] *
35.7 29.8 22.9 21.6 19.8 17.2
Breaker - D/J type [A] (125%) *
45
40
30
30
25
25
Z50 (50 kg/hr nominal)***
Voltage L1 to Neutral [V]
100 120 208 220 240 277
Power [kW] *
4.5
4.5
6.0
6.0
6.0
6.0
Current at rated capacity [A] *
44.6 37.2 28.6 27.0 24.8 21.5
Breaker - D/J type [A] (125%) *
60
50
40
35
35
30
Z100 (100 kg/hr nominal)**/***
Voltage L1, L2 or L3 to Neutral [V]
100 120 208 220 240 277
Power [kW] *
8.9
8.9 11.9 11.9 11.9 11.9
Current at rated capacity [A] *
29.8 24.8 22.9 21.6 19.8 17.2
Breaker - D/J type [A] (125%) *
40
35
30
30
25
25
Z150 (150 kg/hr nominal)**/***
Voltage L1, L2 or L3 to Neutral [V]
100 120 208 220 240 277
Power [kW] *
13.4 13.4 17.9 17.9 17.9 17.9
Current at rated capacity [A] *
44.6 37.2 28.6 27.0 24.8 21.5
Breaker - D/J type [A] (125%) *
60
50
40
35
35
30
Three phase wiring
Z100 (100 kg/hr nominal)***
4-Wire Wye Configuration (4 pole
breaker)
3-Phase Delta Configuration (3 pole
breaker)
Three Phase Line to Line voltage [V]
173 208 360 380 415 480 100 120 208 220 240 277
Voltage L1, L2 or L3 to Neutral [V]
100 120 208 220 240 277 100 120 208 220 240 277
Power [kW] *
8.9
8.9 11.9 11.9 11.9 11.9 8.9
8.9 11.9 11.9 11.9 11.9
Current at rated capacity [A] *
29.8 24.8 22.9 21.6 19.8 17.2 51.5 42.9 39.6 37.5 34.4 29.8
Breaker - D/J type [A] (125%) *
40
35
30
30
25
25
65
55
50
50
45
40
Z150 (150 kg/hr nominal)***
Three Phase Line to Line voltage [V]
173 208 360 380 415 480 100 120 208 220 240 277
Voltage L1, L2 or L3 to Neutral [V]
100 120 208 220 240 277 100 120 208 220 240 277
Power [kW] *
13.4 13.4 17.9 17.9 17.9 17.9 13.4 13.4 17.9 17.9 17.9 17.9
Current at rated capacity [A] *
44.6 37.2 28.6 27.0 24.8 21.5 77.3 64.4 49.5 46.8 42.9 37.2
Breaker - D/J type [A] (125%) *
60
50
40
35
35
30
100
85
65
60
55
50
*Your exact conditions may result in differing power and current.
**Requires three (3) single phase breakers, one for each leg (L1, L2, L3)
***25% capacity derate with 100-120V line to line voltage