16
♦
Next, install a pressure regulator with a high temperature
Fluorocarbon elastomer (Viton) seat no more than 1 meter (3
feet) after the vaporizer outlet. Install this regulator as close to
the outlet of the vaporizer as possible and always at a higher
elevation than the vaporizer outlet to allow any condensed liquid
to travel back to the vaporizer. Never install the regulator more
than 1 meter (3 feet) from the vaporizer. If you are using PE
pipe after the regulator, ensure that it is connected at a
minimum 2 meters (6 feet) after the vaporizer.
♦
Install a pressure gauge in the regulator or at the regulator
outlet.
♦
After the regulator, install a “drip-leg” in the piping or a vapor
filter to collect any residue or heavy-ends from the LPG. The
drip leg should terminate with a valve and a plug for draining.
LPG liquid line size chart (Minimum Pipe Size)
Relief valve
For horizontal installation, no modifications to the relief valve
orientation are required. For vertical installation, ensure that the
relief valve vent is piped in a vertical orientation. This may be
achieved by using a pipe away adapter with a ½” NPT pipe nipple
and ½” NPT F x F elbow, or by switching the LPG outlet adapter
with the pressure relief valve to ensure the pressure relief valve
vents upwards.
Leak test new piping connections during
commissioning.
Note: When mounting vertically, always ensure that the LPG
inlet and the outlet end of the vaporizer are on top.
Capacity of
units
Distance from storage to vaporizer - feet (meters)
MMBtu
(Kcal)
Kg LBS
(GPH)
25
(8)
50
(15)
75
(23)
100
(31)
150
(36)
200
(61)
300
(92)
400
(122)
1.1
(288,792)
25
55
(12.5)
½”
(DN15)
½”
(DN15)
½”
(DN15)
½”
(DN15)
½”
(DN15)
¾”
(DN20)
¾”
(DN20)
¾”
(DN20)
1.8
(446,069)
40
88
(20)
½”
(DN15)
½”
(DN15)
½”
(DN15)
¾”
(DN20)
¾”
(DN20)
1”
(DN25)
1”
(DN25)
1”
(DN25)
2.3
(557,584)
50 110
(25)
½”
(DN15)
½”
(DN15)
½”
(DN15)
¾”
(DN20)
¾”
(DN20)
1”
(DN25)
1”
(DN25)
1”
(DN25)
4.6
(1,155,168)
100 220
(50)
½”
(DN15)
¾”
(DN20)
¾”
(DN20)
¾”
(DN20)
1”
(DN25)
1”
(DN25)
1”
(DN25)
1¼”
(DN32)
6,8
(1,722,690)
150 352
(80)
¾”
(DN20)
¾”
(DN20)
1”
(DN25)
1”
(DN25)
1”
(DN25)
1¼”
(DN32)
1¼”
(DN32)
1¼”
(DN32)
Summary of Contents for ZIMMER