13
Preparing the site
When preparing your site, consider local setback limitations for your
desired storage container(s). Also, consider points of
ingress/egress and other openings into buildings, including any air
intakes. The
ZIMMER
vaporizer is explosion-proof, which means
that it can be mounted next to, on, or near the storage container(s).
For portable applications, the
ZIMMER
(up to 50 kg/hr model)
can be mounted on the storage container. Make sure the mount
touches the vessel in as small an area as possible to avoid
corrosion on the vessel surface.
For stationary applications mount the
ZIMMER
on a wall or
support near the container(s) or on the container (up to 50 kg/hr
model) by using the tank mount kit.
Materials you may need for installation
♦
Storage tank, or cylinder(s) with liquid withdrawal valve(s) also
called “dip tube(s)”, are required.
♦
Excess flow valve(s).
♦
Manifold piping if using multiple cylinders.
♦
Inlet isolation valve with hydrostatic relief valve approved for
liquid LP Gas service (included with
Algas-SDI P/N 80892
)
.
♦
Piping components including forged steel union or removable
compression/flare fittings.
♦
SCH 80 pipe for liquid service, or approved tubing and fittings.
♦
Inlet strainer with No.40 mesh screen (in
Algas-SDI P/N 80892)
♦
Outlet regulator with high temperature Fluorocarbon elastomer
(Viton) seat, (
Algas-SDI P/N 80890
) (Outlet Range 0.21 – 2.10
bar [3-30 psig]).
♦
Outlet isolation valve approved for LP Gas vapor service
(included with
Algas-SDI P/N 80892
).
♦
Wall mount kit up to model Z50. (
Algas-SDI P/N 80885
).
♦
Electrical disconnect switch (See Electrical Specifications in
Appendix).
♦
Metal Terminal box use
Algas-SDI P/N 80895
(Div 1) and
P/N
80896
(Ex) for models up to 50kg/hr.
♦
Wire to connect your
ZIMMER
. Wire type will be determined by
your specific voltage, current and wiring conditions.
Summary of Contents for ZIMMER
Page 2: ......
Page 20: ...19 Wire Length Chart 4 AWG 21 1 mm2 Wire Length Chart 6 AWG 13 3 mm2...
Page 21: ...20 Wire Length Chart 8 AWG 8 36 mm2 Wire Length Chart 10 AWG 5 26 mm2...
Page 45: ......
Page 46: ......
Page 47: ...32...