Troubleshooting
Algas-SDI Operation and Maintenance Manual – P/N – 54000
27
TROUBLESHOOTING TREE #2
PILOT LIGHTS BUT WILL NOT HOLD
CHECK TO SEE THAT THE
PILOT IS IMPINGING ON THE
THERMOCOUPLE BULB,
APPROXIMATELY 3/8” TO 1/2”
CHECK THE THERMOCOUPLE SIGNAL TO
THERMOSTAT CONTROL VALVE. SIGNAL
SHOULD BE 13 TO 30 MILLIVOLTS WHEN
THERMOCOUPLE IS HOT
REPAIR OR
REPLACE PILOT
ASSEMBLY
PILOT IS OK
PILOT IS LOW
SEE TROUBLESHOOTING TREE
#1: PILOT WILL NOT LIGHT
REPLACE
THERMOCOUPLE
SIGNAL OK
SIGNAL LOW