Direct Fired Vaporizer specifications:
BURNER INPUT: 160H
176,900 BTU’s/Hr (51.8 kW) per
burner
GAS CONSUMPTION:
1,000 BTU’s per gallon of propane
vaporized
THERMOSTAT SUPPLY REGULATOR PRESSURE (BURNER ON)*:
15-18” w.c. (37.3 – 44.8 mbar)
BURNER PRESSURE**:
9” w.c. (22.4 mbar)
PILOT BURNER:
2,200 BTU’s/hr (644 W)
NOMINAL OPERATING TEMPERATURE***:
140 to 160
F (60 to 71ºC)
* Regulator Gas Pressure measured between burner regulator and thermostat at the drip leg.
Regulator supply pressure may vary in order to obtain 9” w.c. at the burner. See “Adjusting the
regulator” on page 21.
** Burner pressure measured at the burner pressure test port. See “Adjusting the regulator” on
page 21.
*** Operating Temperature depends on ambient temperature, thermostat settings, and operating
pressures.