DC UPS

 

www.algcom.com.br

 

 

 

 

 

               

Table with values of voltage and input power.

 

 

 

Voltage values 

 

Input current 

Model 

Minimal 

Maximum 

Frequency 

Maximum power 

Minimal 

Maximum 

12V 20A 

100V 

240V 

50/60 Hz 

300W

 

1,25A

 

3A

 

24V 10A 

1,25A 

3A 

24V 15A 

400W

 

1,65A 

4A 

-48V 5A 

300W

 

1,25A 

3A 

-48V 10A 

600W

 

2,5A

 

6A

 

 
                 

The maximum voltage values are 90 - 264V. 

7

 

EQUIPMENT CONNECTION 

 

Measure the output voltage to see if it is suitable for your equipment.  

 

Attention 

Check the voltage of the equipment connected to the DC UPS output. 

 

 
 Use a voltmeter to measure the output voltage.

 

 

 

 
 
 
 
 
 

 

 

 

 
 
 

 
 

8

 

FUNCTION TEST 

 

1)

 

With the load connected to the output or measuring with a voltmeter, unplug the AC power 

cable

 

Equipments 

 
 
 

 

 
Battery bank 

                                       

 
 

Caution

 

 

 
 
 

 

The test may only be performed by a qualified technician. Voltage and energy present can 

cause death or injury if the precautions in this manual are ignored. 

 
 

Disconnect the 

AC power cable. 

Summary of Contents for FN-4800-10-SNMP

Page 1: ...have justacquired an ALGcomproduct Thanks foryour trust at choosing our company We develop products to offer the best and most modern solutions in telecommunications 11510050074_V2 FN FN SNMP DC UPS...

Page 2: ...y present can cause death or injury if the precautions in this manual are ignored Attention Please follow the instructions contained in this manual carefully If you have any doubt please contact quali...

Page 3: ...the DC UPS is being powered by the AC input F CHARGING BATTERY INDICATOR LED Indicates that the DC UPS is charging the battery bank G DISCHARGING BATTERY INDICATOR LED Indicates that the DC UPS is dis...

Page 4: ...s conductor or connect the ground through the AC input connector Attention The connection to protective ground is mandatory It can be connected through power cable or chassis connection N AC INPUT CON...

Page 5: ...the protective ground connection to the ground bus For 48V DC UPS The outputs 0V of the DC UPS are isolated from the ground being optional the connection to the system and grounding For 48V DC UPS To...

Page 6: ...nt power Equipment output current Charger current Equipment power Equipment current Charger current 12V 20A 240W 120W 10A 10A 228W 19A 1A 24V 10A 240W 120W 5A 5A 216W 9A 1A 24V 15A 360W 120W 5A 10A 33...

Page 7: ...ng stage Connect the AC power to the DC UPS Connect the AC power in the back of the DC UPS DC UPS output current Recommended minimum gauge 0 10A 1mm ou 16AWG 10 16A 1 5mm ou 14AWG 16 25A 2 5mm ou 12AW...

Page 8: ...CONNECTION Measure the output voltage to see if it is suitable for your equipment Attention Check the voltage of the equipment connected to the DC UPS output Use a voltmeter to measure the output volt...

Page 9: ...work connect an Ethernet Cable 2 The factory setting is as follows IP 192 168 1 50 User name admin Password admin If you need to return to the initial IP configuration and password press the Reset but...

Page 10: ...he last 10 minutes Indicates if there has been a drop in the AC supply voltage in the last 10 minutes from the time the information is being displayed making it possible to monitor grid instabilities...

Page 11: ...ers Subgroup 2 Charger Parameters OID Description Type Parameters Access 1 3 6 1 4 1 49136 1 1 1 0 Voltage measured at DC UPS output All V Volts Read only 1 3 6 1 4 1 49136 1 1 2 0 Current measured at...

Page 12: ...PS Occurs when the DC UPS is operating at a power above the specified All 0 normal 1 overheating Read only 1 3 6 1 4 1 49136 1 3 6 0 Indicates general overload at DC UPS Occurs when the DC UPS is oper...

Page 13: ...tchdog 5 action for 10 minutes since the last event occurred All 0 normal 1 watchdog actuated in the last 10 minutes Read only 1 3 6 1 4 1 49136 1 7 5 0 Indicates the configured watchdog 6 action for...

Page 14: ...ightning or various atmospheric discharges Overvoltage Protects against the effects of electrical distribution networkmaneuvers Falls Protects against the effect that happens in installations when the...

Page 15: ...of the electronic device piece of equipment 3 Warranty Exclusions The warranty will not cover and it is the sole responsibility of the buyer any damages caused by violation modification change of com...

Page 16: ...of the product have three 3 months warranty For products repaired within the warranty period the warranty expiration date remains the same 6 Warranty Service For products that were not purchased dire...

Reviews: