DC UPS
Connection of battery bank according to
DC UPS voltage.
Check the correct recommendation of the cables in the
table below
.
The battery charger needs to recognize that the battery bank connected to its output is suitable.
Without connecting the batteries, the voltage at the battery connector is 0V.
Below are the voltages that the charger places on the seat according to the loading stage.
Connect the AC power to the DC UPS.
Connect the AC power in the back of the DC UPS!
DC UPS output current
Recommended minimum gauge
0-10A
1mm² ou 16AWG
10-16A
1,5mm² ou 14AWG
16-25A
2,5mm² ou 12AWG
DC UPS output voltage
Minimum battery bank
voltage
Maximum battery bank
voltage
12V
10V
17V
24V
20V
30V
48V
42V
60V
Model
Floating battery
bank voltage
Battery bank equalization
voltage
12V 20A
13,8V
14,4V
24V 15A | 24V 10A
27,5V
28,8V
-48V 5A | -48V 10A
54V
56,7V
6 POWER CABLE CONNECTION
Attention
The connection to protective ground is mandatory. Can be connected via power cable
or chassis connection.