Eve Single manual  |  Version 4.2 |  December 2021

ENGLISH

3. ASSEMBLY AND CONNECTING

3.1 Safety Instructions

Read these instructions carefully before installing the 
charging station. Alfen ICU B.V. is not liable for any 
consequential damage caused by failure to follow the 
instructions in this manual.

REMARK

The installation needs to be performed by a qualified 
electrician who has read this manual and will execute the 
installation in accordance with the IEC 60364 (Electrical 
Installations for Buildings) standard. Failure to do so many 
lead to injury or cause electical health and safety risks.

REMARK

Work on the charging station may not be carried out if the 
atmospheric humidity exceeds 95%.

REMARK

A charging station must always be installed on a power 
circuit intended for that purpose.

 

DANGER!

Installing the station incorrectly may result in fatal injury! 
When working with electricity, failure to comply with 

 

relevant regulations can lead to dangerous and life-

 

threatening situations. 

 

DANGER!

The charging station contains electrical components that 
still contain a charge after being disconnected from the 
system. Always wait 10 seconds after disconnecting 
before beginning to work.

 

DANGER!

The electrical system must be disconnected from every 
power source before performing any installation or 

 

maintenance work!

3.2 Assembly and installation requirements

REMARK

Refer to paragraph 2.7

 

for the safety options and neces-

sary cable diameters for a safe connection.

Ensure that the following requirements for installing the 
Eve Single have been met:

• 

The cable trajectory from the main distributor to the Eve 
Single must be secured against short-circuiting and 
overcurrent with:

  - a B- or C-type circuit breaker (or other, in accordance 

 

  with local standards and regulations), or

  - gG-type fuses (or other, in accordance with local  

  standards and regulations).

• 

The cable trajectory must be equipped with 30-mA fault 
current protection with a type A or B earth leakage 
circuit breaker (type A recommended). The earth leakage 
circuit breaker must be protected against the maximum 
current the charging station can process (20A or 40A)

• 

The cable trajectory and the charging station are part of 
a TN-S system; the equipment must be earthed at the 
main distributor or with an earth pin (TT). An energy grid 
without a neutral conductor is not supported.

• 

The cable trajectory must be installed in accordance 
with the usual local professional standards.

REMARK

Local conditions may influence the installation 

 

requirements.

REMARK

The installation and cables should be installed to match 
the maximum charging current to the input of the charging 
station. This should assume continual load. The cable 
diameters stated in this manual are indicative. The installer 
is always responsible for choosing the right cable diameter 
and complying with the relevant standards and legislation.

When selecting a location to install the Eve, the following 
criteria must be taken into account:

• 

Never install in a potentially explosive atmosphere.

• 

Never install in areas prone to flooding without imple-
menting compensatory measures.

• 

Always fully comply with local technical requirements 
and safety regulations.

• 

An on-site connection is created that complies with the 
specifications in paragraphs 2..7

 

• 

The installation site must have a levelled and solid 
foundation.

• 

Maximum atmospheric humidity of 95%.

• 

Ambient temperature of -25 °C - 40 °C.

• 

A temperature difference within 24 hours < 35 °C.

• 

The recommended installation height is 80 - 120 cm 

Summary of Contents for Eve Single Pro Series

Page 1: ...Eve Single Manual Handleiding Handbuch Manuel K ytt opas S line Pro line...

Page 2: ......

Page 3: ...socket model met stopcontact Modell mit Steckdose mod le avec prise pistorasialla varustettu malli INSIDE BINNENZIJDE INNENSEITE INT RIEUR SIS PUOLI OUTSIDE BUITENZIJDE AUSSEN EXT RIEUR ULKOPUOLELLA...

Page 4: ...t model met stopcontact Modell mit Steckdose mod le avec prise pistorasialla varustettu malli Exterior view Buitenzijde Aussenansicht Ext rieur Ulkopuolella 1 1 3a 3b 2 2 11 10a 8 9 10b 11 11 10a 11 7...

Page 5: ...ilisation of all advanced features of your charging station we recommend that you read this manual carefully and save it for future reference While we have done our utmost to provide you with a comple...

Page 6: ...s 14 2 6 Accessories 15 2 7 Technical specifications for installation 16 2 7 1 External protection according to EV ZE Ready standard 16 3 Assembly and connecting 16 3 1 Safety Instructions 17 3 2 Asse...

Page 7: ...individual components are damaged Usage by children or individuals not able to properly assess the risks associated with using this product Alfen ICU B V shall not be liable in any way for any kind o...

Page 8: ...or plug holder 4 RGB Status LED Interior view Interior view 5 UTP Ethernet connector 5 UTP Ethernet connector 6 RJ11 connector 6 RJ11 connector 7 7 SIM cardholder 8 Terminal block for the power supply...

Page 9: ...Charge card accepted cable connected Communicating with vehicle or charging complete Charging transaction active Status indicators during smart EV charging load balancing The Eve Single S line will i...

Page 10: ...3 2 3 Operation Specific user actions are presented in a sequence that cearly shows the progress and corresponding status indications The first steps can be conducted in any sequence Upon detecting a...

Page 11: ...h h kW kW kWh h Models with fixed charging cable Models with socket Models with socket Models with fixed charging cable Pro line Pro line Pro line Pro line 2 4 1 3 2 4 1 3 2 4 1 3 2 4 1 3 RFID Chargin...

Page 12: ...to undo the action To close the database hold the Master Key in front of the card reader once more Hold the Master Key in front of the card reader Hold the charge pass that you want to add in front o...

Page 13: ...C detector that protects the earth leakage circuit breaker against DC leak age currents The DC detector prevents type A earth leakage circuit breakers from becoming blind to dangerous leakage currents...

Page 14: ...ts default casing colour RAL9016 Other darker colours may have an adverse effect on the product If the product is exposed to lower or higher temperatures continuous operation cannot be guaranteed If t...

Page 15: ...x Quick Installation Guide 1 x M8 nut 4 x M25 x 1 5 For model with fixed charging cable 2 x 2 PRODUCT 2 6 Accessories Item Details Article no Mounting post 803873036 ICU Pole dimensions H x W x D Bas...

Page 16: ...ase 16A 11kW 3 x 20A gG 1 phase 32A 7 4kW 1 x 35A gG 3 phase 32A 22kW 3 x 35A gG Residual current protection possibly i c w circuit breakers Earth leakage circuit breakers 30mA type A or B 4P 3 7kW 11...

Page 17: ...short circuiting and overcurrent with a B or C type circuit breaker or other in accordance with local standards and regulations or gG type fuses or other in accordance with local standards and regula...

Page 18: ...ring and the construction Spirit level Drill machine Torque driver for terminal block connections 3 5 Installation procedure prerequisites The installation location is a solid wall In the surroundings...

Page 19: ...ount the charging station on the wall mount frame Connect the earth wire on the bottom right threaded end of the wall mount frame Use the M8 washer and nut for installation 3 7 Electrical installation...

Page 20: ...tion Screw the front cover back onto the charging station with the Torx T20 wrench Use all six screws for this Models with display Connect the display connector 3 10 Data cable options 3 10 1 Connecti...

Page 21: ...ionality If so check the settings with the Service Installer application to optimally configure the charging station for the local situation More information is available in Appendix B 4 3 Commissioni...

Page 22: ...the smart charge options see Appendix B check the settings and adjust them where necessary to optimally configure the charging station for its location The Service Installer application is divided in...

Page 23: ...isconnect the transpa rent subframe 3 x Torx T20 screw To install a card access the SIM cardholder from the left side This will provide you with more space Be careful not to crush any cables while rep...

Page 24: ...4460127 Eve Single Pro line DE 3PH Cable NG910 60127 904460503 Eve Single S line 1PH T2 NG910 60503 904460505 Eve Single S line 1PH T2S NG910 60505 904460507 Eve Single S line 1PH Cable NG910 60507 90...

Page 25: ...charge point supplier Check powerboard 105 Not able to charge Please call for support Internal error No communication with internal power meter Contact the service department of your charge point supp...

Page 26: ...Cable connected for more than 2 minutes without starting a charging session Reconnect cable and start charging session within 2 minutes Otherwise contact the service depart ment of your charge point...

Page 27: ...ging cable is out of range according to the IEC 61851 norm One specific cable Issues with other charge points Cable broken All cables No issue with oth er charge point Contact the service department o...

Page 28: ...20 metres combined with the P1 port Always check if the communi cation with the smart meter is working properly The quality of the signals depend on several factors Therefore always limit the cable le...

Page 29: ...e network operator Subnet mask of the local network Modbus address of the energy meter Default gateway of the local network Factory settings Options Values SCN NetworkName Name of the SCN Maximum of 8...

Page 30: ...0 1 W SIGNED32 Reactive Power L1 VAr 0 1 VAr SIGNED32 Reactive Power L2 VAr 0 1 VAr SIGNED32 Reactive Power L3 VAr 0 1 VAr SIGNED32 Apparent Power L1 VA 0 1 VA UNSIGNED32 Apparent Power L2 VA 0 1 VA...

Page 31: ...0Mbps network UDP port 36549 inbound outbound Use the DHCP server if possible Without a DHCP server the charging stations obtain an IP address via Auto IP All charging stations are fed from the same p...

Page 32: ...e SCN if you have not purchased this functionality After you receive confirmation for your purchase of this functionality by Alfen the new functionality can be downloaded using the Service Installer a...

Page 33: ...ely For this purpose all local authorities have established collection schemes under which residents can dispose waste electrical and electronic equipment at a recycling centre or other collection poi...

Page 34: ......

Page 35: ...1 0 36 54 93 401 Website www alfen com nl oplaadpunten ev www alfen com en ev charge points Contact Contact Kontakt Contact Yhteystiedot Alfen ICU B V Hefbrugweg 28 1332 AP Almere The Netherlands P O...

Reviews: