background image

CAUTION

: when changing the display scale SCL, the parameters related to the absolute (SPL, SPH, 1SP) and differential (1HY, 1PB,

OS1) temperatures MUST be reconfigured.

TABLE 2

4. OPERATION DESCRIPTION

4.1. C

ONTROLLER STANDBY

. Parameter BAU determine the functions associated with the button 

: with 

BAU=NON

the button is

used to exit from the setup or to abort the autotuning routine; with 

BAU=SBY

the button has an additional function, i.e. it can also be

used to switch on and off the controller: keeping this button pressed for about 3 seconds changes the controller status (on / stand-by).
When it’s on standby, the controller shows OFF, the output is off and it’s not possible to have access to the parameter setup.

4.2. T

YPE OF CONTROL

. The output may operate in the ON/OFF or PID mode: 

1Y=HY

is fixed for ON/OFF control, 

1Y=PID

for PID

control.

4.3. ON/OFF 

CONTROL

. In the ON/OFF mode the output is ON or OFF in relation to the input temperature, set point 

(1SP)

and

hysteresis value 

(1HY)

. The hysteresis indicates the amplitude of deviation of the temperature from the set point in order to reactivate

the output. Increasing the hysteresis value decreases the switcheovers of the output, while decreasing the hysteresis value gives finer
control. For the output to operate in the heating mode, assign a negative value (see Figure 1) to 

1HY

; assign a positive value for control

in the cooling mode (see Figure 2). With 

1HY=0

the output is permanently cut out. After a switchover the output remains in the new

state for a minimum time of 

1CT

seconds irrespective of the temperature value.

4.4. PID 

CONTROL

. In the PID mode the output is ON for a fraction of the cycle time 

1CT

. The cycle time characterises the dynamics

of the system to be controlled and influences the accuracy of the control: the higher the system speed of response the shorter the cycle
time to obtain greater temperature stability and less sensitivity to variations in load. Assign a negative value to 

1PB

to make the output

operate in the heating mode (see Figure 3) and a positive value for control in the cooling mode. With 

1PB=0

the output is permanently

cut out.

4.4.1. P

ROPORTIONAL CONTROL

. The temperature is controlled by varying the time of

activation of the output when the temperature is inside the proportional band (

1PB

).

The nearer the temperature to set point, the less time of activation. A small proportional
band increases the promptness of response of the system to temperature variations, but
tends to make it less stable. A purely proportional control stabilises the temperature
within the proportional band but does not cancel the deviation from the set point. 

INSTRUCTIONS FOR INSTALLATION AND USE.

---

Internal self-test (3 seconds)

E1

In tuning: timeout 1error

5.4

Sensor T1 temperature

E2

In tuning: timeout 2 error

or

Over range or breakage T1

E3

In tuning: over range error

Tun / 5.4

Instrument in auto-tuning

OFF

Controller standby

1SP

1HY

Temp.

The output is on when

the temperature is lower

than the set point

plus hysteresis

Time

Output

The output in the heating mode switches off

when the temperature is higher than set point

on

off

Figure 1

 ON/OFF control in heating mode

1SP

1HY

Temp.

The output is off when

the temperature is lower

than the set point

Time

Output

The output in the cooling mode switches on when

the temperature is higher than the set point plus hysteresis

on

off

Figure 2

 ON/OFF control in cooling mode

1SP

1PB

Temperature

Overshoot

Steady-state error

Process

temperature

Time

Figure 3

 Proportional Control (P) in heating mode

Summary of Contents for AquaPool-11

Page 1: ...NOTICE D INSTALLATION DE MISE EN SERVICE ET D ENTRETIEN INSTALLATION COMMISSIONING AND MAINTENANCE MANUAL MODULES PISCINE SWIMMING POOL HEATERS AquaPool Ver 3 2 du 7 07 2008...

Page 2: ...the water treatment Refer to FIG 1 below The bypass valve should be set to ensure the nominal flow rate is circulated through the AquaPool heating module Pressure access valves or ports should be inst...

Page 3: ...t r sis du thermostat aux valeurs souhait es Voir proc dure de r glage du thermostat ci apr s Le module AquaPool est alors en fonctionnement et la pompe primaire se met en service en fonction de la de...

Page 4: ...rence below the set point It enables to define a temperature at which the pump will be switched on again Out1 LED lit Press for 3 seconds SET buttons then 5 times The display shows HY 1 then the hyste...

Page 5: ......

Page 6: ......

Page 7: ...c dent l aide de la touche Pour afficher la valeur associ e au param tre appuyer sur la touche pour la modifier appuyer en m me temps sur ou On quitte la configuration en appuyant sur la touche ou de...

Page 8: ...rise la dynamique du syst me r guler et influence la pr cision de la r gulation plus la vitesse de r ponse du syst me est grande plus le temps de cycle doit tre petit pour obtenir une plus grande sta...

Page 9: ...es du syst me certaines contraintes de mani re adapter efficacement les param tres de r gulation 5 2 D MARRAGE DE LA FONCTION On acc de la fonction d autor glage en gardant les touches appuy es pendan...

Page 10: ...appuy s jusqu la fin de la phase d autotest Une fois la fonction de recalibrage activ e s lectionner la valeur modifier l aide de ou 0Ad permet la calibration du 0 en introduisant une correction const...

Page 11: ...EL 0422 815320 815303 TELEFAX 0422 814073 www lae electronic com E mail info lae electronic com PARTNER VENEZIA 041 5460713 INSTRUCTIONS POUR L INSTALLATION ET L UTILISATION LTR15T1RE BG LTR15A1RE BG...

Page 12: ...ress the key to exit from setup if the keyboard is not touched for 30 seconds exit is automatic The set point 1SP may also be displayed and adjusted during normal regulator operation by pressing the k...

Page 13: ...ycle time characterises the dynamics of the system to be controlled and influences the accuracy of the control the higher the system speed of response the shorter the cycle time to obtain greater temp...

Page 14: ...to blink on the display Press to confirm selection of the channel the current parameter value is displayed simultaneously Using or change the cycle time to characterise the dynamics of the process to...

Page 15: ...allows a calibration of the top part of the measurement scale with a proportional correction between the calibration point and 0 After having selected the required parameter press to display the valu...

Page 16: ...IA PADOVA 25 31046 ODERZO TV ITALY TEL 0422 815320 815303 TELEFAX 0422 814073 www lae electronic com E mail info lae electronic com PARTNER VENEZIA 041 5460713 INSTRUCTIONS FOR INSTALLATION AND USE LT...

Reviews: