BOSS – Installation, Operation and Maintenance Manual
A l e n c o n S y s t e m s L L C - P a g e
|
32
Soft Pre-Charge of BOSS
Since, the BOSS is a bi-directional optimizer it can pre-charge the output using the BUS side or
the BATT side.
Note:
BUS and BATT used throughout the document are nomenclatures that are
interchangeable based on the direction of power flow
To pre-charge the load, you will need to first
establish the direction of power flow i.e. Bus
BATT or BATT
BUS. Applied voltage will show
up on the HUB in the commensurate field.
When the BUS is the source, the
“Input_Voltage”
header will display the
commensurate source voltage applied
When the BATT is the source, the
“
Output_Voltage”
will
display
the
commensurate source voltage applied
Figure 26: HUB BOSS data