![ALENCON BOSS 1000 Installation, Operation And Maintenance Manual Download Page 16](http://html1.mh-extra.com/html/alencon/boss-1000/boss-1000_installation-operation-and-maintenance-manual_2893956016.webp)
BOSS – Installation, Operation and Maintenance Manual
A l e n c o n S y s t e m s L L C - P a g e
|
15
Technical Specifications
Model
BOSS 1000
BOSS 1500
Number of DCDCs
4
4
DC Bus Specifications
Max DC Bus Voltage
1000 V DC
1500 V DC
Minimum DC Bus Voltage
200 V DC
200 V DC
Battery Voltage Specifications
Operation Voltage Range - Configurable
360 - 1000
360 - 1500
Individual DC-DC Power and Current Specifications
Max Current per DCDC @ 25 Deg C Ambient
19.2 A
14 A
Max Power @ 25 Deg C Ambient
19.2 KW
15.4 KW
Max Current per DCDC @ 50 Deg C Ambient
15 A
10 A
Max Power @ 50 Deg C Ambient
15 KW
11 KW
Efficiency
Peak Efficiency
98%
CEC Weighted Efficiency
97.5%
Standards & Compliance
Certifications
UL1741, IEC 62109-1, CSA C22.2
Environmental
Storage Temperature
-40°C to 60°C
Cooling
Forced Air
Humidity
0-95%
Operating Ambient Temp.
-40°C to 50°C
Form Factor
Packaging
Rack or Rail Mounted, Outdoor Rated
Dimensional Limitations (H x W x D)
Rack Mount: 7U - 8U x 19” x 27”/Rail
Mount: 24.8” x 16.5” x 10.6”
Aux Power
24 V Available
Weight
Rack Mount: 53 KG/Rail Mount: 51 KG
Communications
Modbus RTU Standard/TCP IP optional