Power consumption
General
This section provides input power requirements for RRHs. The term "typical" implies the
site is operating with "busy hour" traffic and at normal room temperatures, with the
batteries on float charge. End-of-life battery reserve times are typically 80% of the initial
battery capacity.
The maximum levels in the table represent expected maximum load when the heater in
the RRH is turned on.
Power consumption for RRHs
The table below lists the power consumption values for the two types of RRHs.
Power Consumption for RRHs
RRH type
Power Draw Typical (watts)
1900 MHz, PCS, 4x40W (25 MHz)
655
1900 MHz, PCS, 4x45W (65 MHz)
715
800 MHz, 2x50W
425
Electrical power requirements for RRHs
Power consumption
....................................................................................................................................................................................................................................
....................................................................................................................................................................................................................................
9927 Dist BTS Outdoor
401-703-516
Issue 1
March 2012
Alcatel-Lucent – Proprietary
Use pursuant to applicable agreements
9-3