DC Power Requirements
•
A means of disconnect must be provided within 10 ft (3 m) of the 7705 SAR-A.
•
A circuit breaker or fuse with recommended current rating 5 A (minimum) to 10 A
(maximum) must be provided.
•
The minimum AWG power conductor for the DC input connections must be based
on the application, and on the local codes, practices, and regulations applicable for
the region.
•
All power cables used on the 7705 SAR-A chassis must meet local safety codes.
AC Power Requirements
•
A standard 120 or 240 VAC outlet is required for the 100W High Voltage Power
Supply.
•
All power cords used on the 7705 SAR-A chassis must meet local safety codes.