3.6 FACP Input
The APD8(F) has two FAI inputs, one which accepts a voltage input, and one that accepts a dry
contact input. Consult the appropriate section below for Terminal Connections for the type of
connection being used. See Appendix C for more information and specific wiring diagrams for the
FACP Input.
3.6.1 Voltage FACP Input
y
FACP +
FACP Input Positive
y
FACP -
FACP Input Common
3.6.2 Dry Contact FACP Input
y
FACP T+
One leg of the FACP Dry Contact Input (This terminal is positive with respect
to DC Common)
y
FACP T-
The other leg of the FACP Dry Contact Input
NOTE -
If the APD8(F) is being used with a power supply which has its own FAI Input, the supply’s
FAI input may be used to control the APD8(F) board. See Appendix D for more information.
3.7 FACP AUX Output
The FACP AUX output is a relay output which follows the FACP Input state. Typically, this output is
used to activate the FACP Input on additional APD8(F) boards. See Appendix C and Appendix D for
wiring details.
Fig. 3.6
~ ~
~ ~
FIRE ALARM
INPUT INDICATOR
FIRE ALARM OVER RIDE
TRIP TERMINALS
APD8(F) Installation Instructions
10/9/2007, 12:19:29 PM
Page 10 of 24
AlarmSaf
65A Industrial Way, Wilmington, MA 01887 978 658 6717 www.alarmsaf.com
52-254 Rev B01