5.5 Troubleshooting
Verify the Zone Output wiring
Zone Output wired incorrectly
Verify the FACP Input configuration
FACP Input wired incorrectly
See Section 5.3
Output Configuration Jumper set
incorrectly
Output not dropping power on a
FACP input
Contact AlarmSaf
Other Problem
Verify that the FACP input is not
activated.
FACP Input active
Verify output integrity and replace
fuse, or remove output load to reset
PTC.
Blown Fuse / Tripped PTC
See Section 5.3
Output Configuration Jumper set
incorrectly
Verify the output is configured
properly
Zone Output wired incorrectly
Verify the input is configured properly
Zone Input in the wrong state
Verify power is present on the power
input terminals. If J1 and J2 are
removed, BOTH power inputs must
be powered.
No power input
See Section 5.1
J1 and J2 set incorrectly
No power on output(s)
Solution
Possible Cause
Condition
APD8(F) Installation Instructions
10/9/2007, 12:19:29 PM
Page 16 of 24
AlarmSaf
65A Industrial Way, Wilmington, MA 01887 978 658 6717 www.alarmsaf.com