ALARM CONTROLS CORPORATION

MODEL ZAC-32

32 ZONE ANNUNCIATOR/CONTROLLER

DESIGNED FOR ZONE ANNUNCIATION AND MONITORING

32 HARD WIRED ZONES CAN BE NORMALLY-OPEN OR NORMALLY-CLOSED

ZONE WIRING RUNS CAN BE AS FAR AS 10,000 FEET FROM CONTROL CABINET

UP TO FOUR REMOTE CONSOLES CAN BE ADDED TO A SYSTEM 

CONTROL CABINET CONNECTED TO CONSOLE WITH FOUR WIRE CABLE

REMOTE CONSOLE CAN BE LOCATED UP TO 1000 FEET FROM CONTROL CABINET

BUILT-IN AUDIBLE SIGNAL, SOUND LEVEL IS 80dB @ 3 FEET

SIXTEEN FOUR DIGIT ACCESS CODES 

ALL ZONE CONTROL AND ZONE STATUS ON REMOTE CONSOLE

ZONE BY-PASS CAPABILITY, ZONE BY-PASS OUTPUT, DAY ZONE BYPASS

THIRTY-TWO RED LED ZONE STATUS INDICATORS

LOW STAND-BY BATTERY OUTPUT, AC POWER FAILURE OUTPUT

ALL FIELD WIRING TERMINATED IN CENTRALLY LOCATED CONTROL CABINET

Summary of Contents for ZAC-32

Page 1: ...A SYSTEM CONTROL CABINET CONNECTED TO CONSOLE WITH FOUR WIRE CABLE REMOTE CONSOLE CAN BE LOCATED UP TO 1000 FEET FROM CONTROL CABINET BUILT IN AUDIBLE SIGNAL SOUND LEVEL IS 80dB 3 FEET SIXTEEN FOUR DI...

Page 2: ...DUCTOR WIRE DESKTOP ANNUNCIATOR CONECTED TO CABINET WITH 22 GA SHEILDED 4 CONDUCTOR WIRE DESKTOP ANNUNCIATOR SIZE 16 2 L x 8 W x 2 8 D CABINET SIZE 13 H x 11 75 W x 3 5 D RACK MOUNTED ANNUNCIATOR STAN...

Page 3: ...MENTS 2 AC POWER 2 STANDBY BATTERY 2 EARTH GROUND 2 ZONE INPUTS ZAC 32 2 ZONE INPUTS ZAC 32S 3 ZONE TERMINAL DESIGNATIONS 3 CONNECTING PROCESSOR TO PRINTER INTERFACE 4 AUXILIARY VOLTAGE OUTPUTS 4 EXTE...

Page 4: ...NE PROCESSOR FROM THE REMOTE CONSOLE OVER A FOUR CONDUCTOR CABLE UP TO FOUR REMOTE CONSOLES CAN BE ADDED TO THE SYSTEM FOR ANNUNCIATION AND CONTROL AT MULTIPLE LOCATIONS REMOTE CONSOLES CAN BE LOCATED...

Page 5: ...HAVE STANDBY POWER IF FUSE IS BLOWN THE BATTERY FUSE IS LOCATED TO THE RIGHT OF TERMINAL 7 ON THE PRINTED CIRCUIT BOARD C EARTH GROUND THIS UNIT HAS EFFECTIVE LIGHTNING PROTECTION ONLY WHEN GROUNDED A...

Page 6: ...ATION 1 19 21 20 21 _ _ _ _ _ _ _ _ 17 43 45 44 45 _ _ _ _ _ _ _ _ 2 19 22 20 22 _ _ _ _ _ _ _ _ 18 43 46 44 46 _ _ _ _ _ _ _ _ 3 19 23 20 23 _ _ _ _ _ _ _ _ 19 43 47 44 47 _ _ _ _ _ _ _ _ 4 19 24 20...

Page 7: ...AXIMUM TOTAL CURRENT AVAILABLE FROM THESE OUTPUTS IS 700 MA THIS TOTAL OF ALL OUTPUTS SHOULD NOT BE EXCEEDED USE THE PROVIDED CHART TO TOTAL THE SUM OF THE OUTPUTS VOLTAGE OUTPUT TERMINALS CURRENT USE...

Page 8: ...CALCULATING THE TOTAL CURRENT USED BY THE SYSTEM THE REMOTE CONSOLE IS TERMINATED WITH AN EIGHT CONDUCTOR MODULAR CORD AN EIGHT CONDUCTOR MODULAR JACK IS SUPPLIED TO TERMINATE THE CABLE RUN BETWEEN TH...

Page 9: ...C 28 MA NOTE TOTAL CURRENT FROM ALL OUTPUTS NOT TO EXCEED 800 MA FUSES BATTERY FUSE 2 5 SB 3 AG AUXILIARY POWER FUSES 5 x 20MM 500MA ZONE PARAMETERS LOOP RESPONSE TIME 250 MS TO ACTIVATE 125 MS TO RE...

Page 10: ...PREPARED BY THE FEDERAL COMMUNICATION COMMISSION HELPFUL HOW TO IDENTIFY AND RESOLVE RADIO TV INTERFERENCE PROBLEMS THIS BOOKLET IS AVAILABLE FROM THE U S GOVERNMENT PRINTING OFFICE WASHINGTON DC 204...

Page 11: ......

Page 12: ...PLAY CONSOLE THE REMOTE CONSOLE DISPLAYS AND CONTROLS ZONE STATUS AND SYSTEM CONDITIONS THE CONSOLE CONTAINS A DIGITAL KEYPAD ZONE SYSTEM INDICATORS AND AN AUDIBLE SIGNAL A DIGITAL KEYPAD THE DIGITAL...

Page 13: ...THE AUDIBLE ANNUNCIATOR IS NOT RESET THE AUDIBLE SIGNAL WILL SOUND AFTER THE LAST KEY IS PRESSED D MEMORY RESET WHEN A ZONE HAS BEEN VIOLATED THE ZONE MEMORY IS SET IN ORDER TO MONITOR THE ZONE STATU...

Page 14: ...ZONE 2 INDICATOR WILL FLASH BYPASS STATUS OUTPUT WILL TURN ON THE FOLLOWING IS AN EXAMPLE OF THE ZONE UN BYPASS FUNCTION TO UN BYPASS ZONE NUMBER 30 1 LOAD A VALID FOUR DIGIT ACCESS CODE THEN PRESS PO...

Page 15: ...ODE 01 1865 02 9506 03 5198 04 7357 05 9274 06 4742 07 2645 08 2405 09 7928 10 9258 11 8296 12 8320 13 9078 14 9536 15 8878 16 4530 B ZONE DESIGNATIONS STANDARD ZONES 1 24 DAY ZONES 25 32 ALARM CONTRO...