28
RWF50 PARAMETER SETTING
Shown at the right is the Parameter level display.
The Actual Value display (red colored – the upper one), shows
the parameter’s actual value. The setpoint display, (green – the
lower one) shows the parameter yor are adjusting or viewing.
You can adjust the values for Pb1, q, HYS1, HYS2, HYS3, rt
and dt values depending on your specific configuration.
You can adjust the values, within limits, for SP1,SP2 and DsP, also view InP1 and Y depending on
your specific configuration.
To alter ‘SP1’, ‘SP2 and ‘DsP’ you can use the setting principle map. 0pr is displayed in the user
level. Press Enter and SP1 is displayed on the screen. Press Enter once and SP1 starts blinking. The
value can be set by using and and be confirmed by pressing .
The timeout period is 180 seconds and RWF 50 will accept the last confirmed value to be valid
whether if the parameter is not saved within this period.
RWF50 parameter setting also can be setted by using
Self-Tuning Function
.
For parameter setting of RWF50
Self-Tuning Function is recommended
Auto-tune is a self-setting software function, that is integrated into the RWF50 controller, and
can be repeated as often as desired. Auto-tune tests the reaction, in the modulating mode of
operation, of the-control loop, to steps in the actuator position, according to a special
procedure. The data, during the forced oscillations, is then recorded, and used to calculate
new values, that are optimized for your specific controlled system.
Summary of Contents for ALG 120/M
Page 2: ...Code A 6 1 5i Revision Date 071116 Print Date 071116...
Page 3: ...ALARKO Models ALG 200 M ALG120 M Natural Gas LPG Burners ASSEMBLY OPERATION MAINTENANCE...
Page 16: ...16 DIMENSIONS mm ALG 200 M ALG 200 M LPG ALG 200 M ALG 200 M LPG ALG 120 M ALG 120 M LPG...
Page 26: ...26...
Page 34: ...2 34 VALVE PROVING SYSTEM VPS 504 SO2 Dimensions Lockout Run...
Page 53: ...53 WIRING DIAGRAMS RWF50 ALG 200 M and ALG 200 M LPG...
Page 54: ...54 WIRING DIAGRAMS RWF50 ALG 120 M and ALG 120 M LPG...
Page 55: ...WIRING DIAGRAMS SDC 12 31 ALG 200 M and ALG 200 M LPG...
Page 56: ...56 WIRING DIAGRAMS SDC 12 31 ALG 120 M and ALG 120 M LPG...