AIR DAMPER MOTOR & AIR FLOW ADJUSTMENT FOR MODULATING
BURNERS (SQN 30.401A2700 )
20
Siemens SQN30 actuators are used on modulating burners. There are 5 cams on this actuator.
(II)
0 point cam.
(III)
Minimum capacity adjustment cam.
(I)
Maximum capacity adjustment cam.
(V)
Min – max switching cam.
(IV)
Not actively used.
SQN 30 damper motor stroke is 90° and
the time to achieve this stroke is 30s.
Note : Proper 0 (Zero) adjustment must be
checked. The air damper must be fully closed
when (II) cam indicates 0°.
Stage Switching cam; from 1st to 2nd
stage. (Must be adjusted 10-15°
smaller
than the 2nd stage point).
0 point cam
Min. Capacity (1st) adjustment cam.
Max. Capacity (2nd) adjustment cam.
AIR DAMPER MOTOR & AIR FLOW ADJUSTMENT FOR MODULATING
BURNERS (SQN 70.664A20 )
BLUE
: 0 point adjustment cam
RED
: Max. Capacity adjustment cam
ORANGE
: Min. Capacity adjustment
BLACK
: Stage Switching cam; from 1st to
2nd stage. (Must be adjusted 10-15°
smaller
than the 2nd stage point).
SQN 70 damper motor stroke is 90° and
the time to achieve this stroke is 30s.
Note : Proper 0 (Zero) adjustment must be
checked. The air damper must be fully closed
when (II) cam indicates 0°.
Summary of Contents for ALG 120/M
Page 2: ...Code A 6 1 5i Revision Date 071116 Print Date 071116...
Page 3: ...ALARKO Models ALG 200 M ALG120 M Natural Gas LPG Burners ASSEMBLY OPERATION MAINTENANCE...
Page 16: ...16 DIMENSIONS mm ALG 200 M ALG 200 M LPG ALG 200 M ALG 200 M LPG ALG 120 M ALG 120 M LPG...
Page 26: ...26...
Page 34: ...2 34 VALVE PROVING SYSTEM VPS 504 SO2 Dimensions Lockout Run...
Page 53: ...53 WIRING DIAGRAMS RWF50 ALG 200 M and ALG 200 M LPG...
Page 54: ...54 WIRING DIAGRAMS RWF50 ALG 120 M and ALG 120 M LPG...
Page 55: ...WIRING DIAGRAMS SDC 12 31 ALG 200 M and ALG 200 M LPG...
Page 56: ...56 WIRING DIAGRAMS SDC 12 31 ALG 120 M and ALG 120 M LPG...