Subject to changes in line with technical progress.
37
3059570
Assembly
Supply air temperature sensor
To measure the exact supply air temperature, the supply air sensor must be installed in the duct behind the air handling
unit. Ideally, it should be mounted directly on the supply air duct outlet to take into account any interference in the duct
network.
2
3
1
Fig. 24 Supply air temperature sensor
1
Position of outdoor air temperature sensor (ODA)
3
Position of supply air temperature sensor (SUP)
2
Position of extract air temperature sensor (ETA)
5.6.6
Connection of electric air heater (ELE option)
An electric air heater is optionally available for heating the supply air.
WARNING
Risk of injuries due to incorrect or faulty connection.
Only have the electrical connection carried out by an approved electrician.
Only have assembly, servicing and maintenance carried out by qualified staff.
Wear personal protective equipment.
CAUTION
Risk of burns due to contact with the hot electric air heater.
Wait until the hot electric air heater has cooled down.
Wear personal protective equipment.
The air heater is included in the regulation for the room or supply air temperature and is continuously regulated accord-
ing to temperature requirements. The air heater is equipped with an integrated safety temperature limiter and air flow
monitor.
A separate mains supply is required for the electric air heater.
Connect the air heater electrically according to the circuit diagram.
Attach a warning sign.
NOTE
More information on the power consumption for the EASYAIR
®
flat unit can be found in the
circuit diagram supplied.