Specifications
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 ·
5
2 Specifications
Table 2.1 General specification
Device
230.1.x
230.2.x
230.4.x
24.1.x
24.2.x
24.4.x
Power supply
230 (94…264) V AC;
50 (47…63) Hz
24 (19…30) V DC
Power consumption, max
10 VA
17 VA
10 W
10 W
Galvanic isolation
2830 V
1780 V
Appliance class
II
III
Integrated voltage source
-
24±3 V DC
100 mA
-
-
Galvanic isolation
-
1780 V
-
-
Inputs
Digital
8
Analog *
-
4
-
4
Outputs
Digital (relay)
6
8
6
8
Analog
-
2
-
2
Programming
Software
akYtec ALP
Interface
Mini USB 2.0
Program cycle, min
1 ms
Function buttons
6
LEDs
F1 (green), F2 (red), programmable
LCD display
2x 16 digits, backlight adjustable
Language
English
RS485 interface **
2-pole plug-in terminal block
Protocols
Modbus RTU/ASCII (master/slave)
Baud rate
9.6…115.2 kbit/s
Interface card
PR-IC485 (max. 2)
Galvanic isolation
1500 V
Dimensions
123 x 108 x 58 mm (with terminal blocks)
Mounting
DIN rail (35 mm)
Weight
approx. 350 g
IP code
IP20
* Analog inputs AI1…AI4 can also be configured as digital inputs
** For x.x.1 and x.x.2 models only
Table 2.2 Digital inputs
Device
230.1.x
230.2.x
230.4.x
24.1.x
24.2.x
24.4.x
Input signal
Switch contact
Switch contact
PNP with open collector
Digital signals -
3…+30 VDC
Input voltage
230 V AC
24 V DC
Input voltage, max
264 V AC
30 V DC
Logical 1
159…264 V (0.75…1.5 mA)
15…30 V (5 mA)
Logical 0
0…40 V (0…0.5 mA)
-
3…+5 V (0…1 mA)
Pulse length, min
50 ms
2 ms
Response time, max
100 ms
30 ms
Galvanic isolation
in groups of 4 (1-4, 5-8)
Test voltage between
input groups
1780 V