351652602 Ed. 03
31
Defrost
Level 1
Level 2
Description
Values Min. Def. Max.
dEF
d0
Defrost frequency (time between 2 starts)
h.
0
6
96
d1
Maximum defrost duration (0=defrost deactivated)
min.
0
*
255
d2
Type of message during the defrost: 0=sign of the real temperature; 1=sign of
the temperature at the start of the defrost;
2=sample of the dEF message
0
2
2
d3
Maximum message duration
(time added at the end of the defrost process)
min.
0
5
255
d4
Final defrost temperature (by sensor) (If I00
¹
1)
ºC/ºF -50 8.0 50
d5
Defrost on connecting the unit: 0=NO, first defrost according to d0;
1=YES, first defrost according to d6
0
0
1
d6
Delay of the defrost start on connecting the unit
min.
0
0
255
d7
Type of defrost: 0=resistors; 1=air/fans
2=hot gas
0
*
2
d8
Time calculation between defrost periods:
0=total real time 1=sum of COOL time connected
0
0
1
d9
Drip time when a defrost finishes
(stop COOL and fans)
min.
0
1
255
EP
Output to level 1
Evaporator fans
Level 1
Level 2
Description
Values Min. Def. Max.
FA
n
F0
Fans stop temperature
ºC/ºF. -50 45
50
F1
Sensor 2 differential if fans are stopped
ºC/ºF 0.1 2.0 20.0
F2
Stop fans when the compressor stops 0=no 1=yes
0
0
1
F3
Status of the fans during the defrost 0=stopped; 1=running
0
*
1
F4
Start-up delay after defrost (if F3=0)
Only actuates if higher than d9
min.
0
2
99
F10
Fan control type 0=ON/OFF 1=frequency inverter
0
*
1
EP
Output to level 1
* According to the set-up wizard.
Summary of Contents for AKO-16526
Page 38: ...351652602 Ed 03 38...
Page 39: ...351652602 Ed 03 39...