351652602 Ed. 03
28
Configuration
Condensed programming menu
This allows for the most-used parameters to be quickly configured. Press the SET key for 3 seconds to access it.
Parameters
Level 2
Description
Values Min. Def. Max.
SP
Temperature setting (Set Point)
ºC/ºF
-50
0.0
99
C1
Sensor 1 differential (Hysteresis)
ºC/ºF
0.1
2.0 20.0
d0
Defrost frequency (time between 2 starts)
h.
0
6
96
d1
Maximum defrost duration (0=defrost deactivated)
min.
0
*
255
d4
Final defrost temperature (by sensor) (If I00
¹
1)
ºC/ºF
-50
8.0
50
SH
Superheating set point
ºK
0.1
8
40
F3
Status of the fans during the defrost 0=stopped; 1=running
0
*
1
A1
Alarm for maximum in sensor 1 (it must be higher than the SP)
ºC/ºF
A2 99.0 99.0
A2
Alarm for minimum in sensor 1 (it must be lower than the SP)
ºC/ºF
-50
-50
A1
Condensed programming menu
Temperature
indication
20 sec.
20 sec.
3 sec.
Parameters
Save change
s
Do not save changes
Values
Change
parameter
Change
value
OUT OF
PROGRAMMING
IN
PROGRAMMING
* According to the set-up wizard.