Superheating SET POINT
Enter the desired optimum superheating value.
Assistant
The first time the unit receives the power supply, it will enter into ASSISTANT
mode.
The display will show the message
In{
flashing at
0
.
The buttons
and
change the value, the
SET
button accepts
the value and moves on to the next step.
Step 1:
Select the most suitable InI option based on the type of installation to be carried out and press
SET
.
The available options will be shown in the following table:
InI
Type of installation
Parameters
Control of
the compressor
Pump
Down
Defrost
Evap.
Fans
Pd o00 o20 I00 I10 I11 I20 I21 I30 I31 d1 D7 F3
0
Demo mode: it displays the temperature but does not regulate the temperature
1
No
No
Electric
Yes
0
0
*
2
0
0
0
0
*
* 20 0
0
2
Yes
Yes
Electric
Yes
1
1
*
2
7
1
0
0
*
* 20 0
0
3
Yes
No
Electric
Yes
0
1
*
2
0
0
0
0
*
* 20 0
0
4
No
No
Air
Yes
0
0
*
1
0
0
0
0
*
* 20 1
1
5
Yes
Yes
Air
Yes
1
1
*
1
7
1
0
0
*
* 20 1
1
6
Yes
No
Air
Yes
0
1
*
1
0
0
0
0
*
* 20 1
1
7
Yes
Yes
Hot gas
Yes
1
1
*
2
7
1
7
1
*
*
5
2
0
8
Yes
No
Hot gas
Yes
0
1
*
2
0
0
7
1
*
*
5
2
0
* If
u00
=2:
o20
=3,
I30
=0,
I31
=0
If
u00
≠
2:
o20
=0,
I30
=9
If options 2, 5, or 7 are chosen, check the configuration of parameter I11 according to the pressure
switch type used.
Step 2:
Choose the type of expansion valve to be used:
u00=0
Liquid solenoid valve +
thermostatic expansion valve
u00=1
PWM-controlled solenoid valve
u00=2
Electronic expansion valve (requires an external controller for
the EEV. For more information, please refer to the
available on our website)
If u00=0 is chosen, steps 4, 5, 6, 7, 8, 9 and 11 are not displayed.
If u00=2 is chosen, step 3 is not displayed.
1
/
/ SET
2
/
/ SET
3
/
/ SET
4
/
/ SET
5
/
/ SET
6
/
/ SET
7
/
/ SET
8
/
/ SET
9
/
/ SET
10
/
/ SET
11
/
/ SET
12
/
/ SET
1
/
/ SET
2
/
/ SET
3
/
/ SET
4
/
/ SET
5
/
/ SET
6
/
/ SET
7
/
/ SET
8
/
/ SET
9
/
/ SET
10
/
/ SET
11
/
/ SET
12
/
/ SET