Warnings
-If the device is used without adhering to the manufacturer's instructions, the device safety require-
ments could be compromised. Only sensors supplied by AKO must be used for the unit to operate
correctly.
-From -40°C to +20°C, if the NTC sensor is extended to 1000m with at least a 0.5mm
2
cable, the maximum
deviation will be 0.25°C (cable for sensor extension ref. AKO-15586. Earth the cable mesh at one end only).
-The product should be installed in a place protected from vibrations, water and corrosive gases, where the
ambient temperature does not exceed the value indicated in the technical data.
-For the reading to be correct, the sensor should be used in a place without heat influences apart from the tem-
perature you want to measure or control.
-The IP65 protection degree is only valid with the protection cover closed.
-The IP65 protection degree is only valid if the cables enter the device using a tube for electric condu
gland with IP65 or above. The gland should be the right size for the diameter of the tube used.
-Do not spray the unit directly with high-pressure hoses, as this could damage it.
IMPORTANT:
-The AUXILIARY relays are programmable, and their operation depends on the configuration.
-The function of the digital inputs depends on the configuration.
-The recommended currents and powers are the maximum working currents and powers.
Maintenance
Clean the surface of the unit with a soft cloth, water and soap.
Do not use abrasive detergents, petrol, alcohol or solvents, as this might damage the unit.