351652602 Ed. 03
34
Basic configuration
Level 1
Level 2
Description
Values Min. Def. Max.
bcn
b00
Delay of all functions on receiving power supply
min.
0
0
255
b01
Cold room light timing
min.
0
0
999
b10
Password function 0=inactive
1=parameter access lock 2=keypad lock
0
0
2
PAS
Password
0
0
99
b20
MODBUS address
1
1
247
b21
Communication speed: 0=9600 bps 1=19200 bps
2=38400 bps 3=57600 bps
bps
0
0
3
b22
Audible alarm enabled 0=no 1=yes
0
1
1
b23
Lower display function: 1=sensor S2, 2=sensor S3, 3=sensor S4, 4=sensor
S5, 5=superheating, 6=pressure sensor, 7=% EEV, 8=% eFAN, 9=carousel,
10=off
1
*
10
Unt
Working units 0=ºC 1=ºF
0
0
1
EP
Output to level 1
Inputs and outputs
Level 1
Level 2
Description
Values Min. Def. Max.
InO
I00
Probes connected: 1=sensor 1 (cold room), 2=sensor 1 (cold room) + sensor
2 (evaporator)
1
2
2
I10
D1/S3 input configuration: 0=deactivated, 1=door contact, 2=external alarm,
3=severe external alarm, 4=change SP, 5=remote defrost,
6=defrost lockout, 7=low pressure switch, 8=remote activation in Stand-by
mode, 9=product temperature
0
*
9
I11
Digital input polarity D1: 0=activates on closing, 1=activates on opening
contact
0
0
1
I20
D2/S4 input configuration: 0=deactivated, 1=door contact, 2=external alarm,
3=severe external alarm, 4=change SP, 5=remote defrost,
6=defrost lockout, 7=high pressure switch for hot gas, 8=remote activation of
Stand-by mode, 9=product temperature, 10=defrost 2
nd
evaporator
0
*
10
I21
Digital input polarity D2: 0=activates on closing, 1=activates on opening
contact
0
0
1
I30
D3/S5 input configuration: 0=deactivated, 1=door contact, 2=external alarm,
3=severe external alarm, 4=change SP, 5=remote defrost,
6=defrost lockout, 7=remote activation of Stand-by mode, 8=rroduct temper-
ature, 9=superheating temperature (Sh)
0
*
9
I31
Digital input polarity D3: 0=activates on closing, 1=activates on opening
contact
0
0
1
* According to the set-up wizard.