Leakage checking
F
Check a gas-leakage of the connection portion of the piping.
F
If there is no leakage found, open 2-way again, turn the valve spindle coun-
ter-clockwise until it stops.
F
If there is leakage found, re-tighten the connecting portion with wrench. If the
leakage persists, locate a leakage and repair it until leakage ceases.
l
Air purging
F
To purge the air, push the pin on the service port of 3-way valve for three sec-
onds with a hexagonal wrench, wait for
one
minute.
F
Repeat the operation
three times
.
No leakage found
Leakage found
Open 2-way valve again, turn the
valve spindle counter-clockwise
until it stops
Re-tighten the connecting portion with
wrench
Leakage ceases
Leakage
persists
Locate a repair leak
Purge the air, push the pin on the service port of the 3-way valve for three
seconds with a hexagonal wrench, wait for one minute. Repeat the operation for
three times.