Ultrasonic Fuel Level Sensor Manual
Updated until firmware 405p & 1.0.3816
- 11 -
2. Mounting and installation
A) Invasive UFLS
Before we go any further it is important to read the following information in regards to
installation.
1. The sender must not be mounted closer than 150mm from the center of the sender
to sides of the tank, baffles or other intrusions.
2. Only use on tanks greater than 200mm in depth but no greater than 2000mm deep.
3. Sender must be mounted parallel to the surface of the liquid.
4. Do not install on flexible tanks that may bulge/distort as fluid levels change.
5. Check the unit to insure it is calibrated to suit tank shape, depth and fluid type.
6. Make sure that sender protrusion is NOT in contact with any object including
sealants when mounted.
7. Use gasket and fittings as provided.
8. Mount above deepest point of the tank.