11
Subject to technical amendments without prior notice | 83059300iUK | ait-deutschland GmbH
6.1 Heating circuit
Safety module and shut-off ball valves
1.
Take the safety module and the shut-off ball
valves out of the accessory pack and fit them to
the connections provided. Use seals from the ac-
cessory pack.
2. Lay the safety discharge of the safety valve into
the drain via a funnel waste trap according to the
relevant standards and guidelines.
It is essential that the safety discharge is connect-
ed.
Heating water inlet and outlet
1. Establish the hydraulic connection to the unit.
2. Establish the hydraulic connection to the heating
circuit.
Position of the connections: “Dimensioned draw-
ings”, page 22
6.2 Expansion vessel
The expansion vessel for the heating circuit is integrated.
Always inspect whether the size of the expansion ves-
sel is large enough for the system. If necessary, an ad-
ditional expansion vessel must be installed on site in
accordance with the relevant valid standards.
NOTE
The admission pressure of the expansion
vessel must be adjusted to the system (ap-
prox. 0.5 bar less than the system filling pres
-
sure) in accordance with calculation accord-
ing to the relevant standards (EN 12828).
6.3 Hydraulic connection for the
domestic hot water tank
Connect the domestic hot water tank according to DIN
1988 and DIN 4753 Part 1 (or the standards and direc-
tives applicable locally).
Position of the connections: “Dimensioned draw-
ings“, page 22
The working overpressure cited on the name plate
must not be exceeded. Install a pressure reducer if re-
quired.
The sensor for the domestic hot water preparation is
already connected in the switch box.
IMPORTANT
The electrical conductivity of the domestic hot water
must be > 100 µS/cm and must lie within the drink
-
able water quality limits.
Summary of Contents for HSDV 12.1M3
Page 1: ...UK 83059300iUK Accessories for heat pumps Operating Manual Hydraulic Station...
Page 41: ...41 Subject to technical amendments without prior notice 83059300iUK ait deutschland GmbH...
Page 42: ...42 Subject to technical amendments without prior notice 83059300iUK ait deutschland GmbH...
Page 43: ...43 Subject to technical amendments without prior notice 83059300iUK ait deutschland GmbH...
Page 44: ...UK ait deutschland GmbH Industriestra e 3 D 95359 Kasendorf www ait deutschland eu...