Notes.
1. Softstarters Do Not Fix Power Problems!
2.
Surestart 6 does not have an external start capacitor. (It’s internal).
3.
Where a “hardstarter” is fitted across the run capacitor this
must
be removed.
4
. Product bulletin PB085, contains wiring connection details for each model.
Please obtain a copy of this if required. See “professional” web site
www.airwell.com.au
the pass word or faxed copy is available from tech
support on 1800 1800 04 Prompt 4.
Multiple Models
Multiple Wiring!
Refer Product
Bulletin PB085.
Softstarters
“Surestart 6” - 8.6 to 15 kW
Fault indication LED.
2 Flashes every 5 secs. Ready to go. Standby.
1 Flash per second. In 3 min delay cycle.
1 Flash every 10 sec. External Fault.
(Wrong wiring, Capacitor fault or Comp fault).
10 Flashes per Sec. Low or high voltage.
Surestart 6.
Comp run Cap.
Fault indication
LED.
Page
33