DC VOLTAGE IN THERMISTORS
Temp
Volts
All other
DUO De-icer
Volts
Temp
Volts
All other
DUO De-icer
Volts
-20 4.554
24 2.555
4.6
-19 4.529
25 2.500
4.5
-18 4.502
26 2.445
-17 4.475
27 2.391
-16 4.446
28 2.338
-15 4.417
29 2.284
-14 4.386
30 2.232 4.02
-13 4.354
31 2.180
-12 4.322
32 2.128
-11 4.287
33 2.077
-10 4.252
7.65
34 2.027
-9 4.216
7.59
35 1.978 3.56
-8 4.178
7.52
36 1.929
-7 4.140
7.45
37 1.881
-6 4.100
7.38
38 1.834
-5 4.059
7.31
39 1.798
-4 4.017
7.23
40 1.742 3.14
-3 3.974
7.15
41 1.698
-2 3.930
7.07
42 1.654
-1 3.885
6.99
43 1.611
0 3.839 6.91
44 1.569
1 3.792 6.83
45 1.527 2.75
2 3.744 6.74
46 1.487
3 3.695 6.65
47 1.447
4 3.646 6.56
48 1.409
5 3.595 6.47
49 1.371
6 3.544 6.38
50 1.334 2.4
7 3.492 6.29
51 1.298
8 3.443 6.19
52 1.263
9 3.388 6.09
53 1.228
10 3.333
6.00
54 1.195
11 3.278
5.9
55 1.162 2.09
12 3.223
5.8
56 1.130
13 3.168
5.7
57 1.009
14 3.113
5.6
58 1.069
15 3.257
5.5
59 1.040
16 3.002
5.4
60 1.011
17 2.946
5.3
61 0.983
18 2.890
5.4
62 0.956
19 2.833
5.1
63 0.929
20 2.777
5
64 0.904
21 2.722
4.9
65 0.879
22 2.666
4.8
66 0.854
23 2.610
4.7
67 0.831
All Three Thermistors on the unit have the same resistance values and therefore
the same voltage readings, except for the “Duo de-icer volts,” the voltage reading
on the outdoor coil on the duo units fitted with a double de-icer or typhoon PCB.
Page
22
Summary of Contents for K CassetteSeries
Page 14: ...RC4 REMOTE CONTROL Page 12...
Page 15: ...RC4 MODES OF OPERATION FUNCTIONS FEATURES Page 13...
Page 16: ...Page 14...