- On models K 30 RCF and K 45 RCFA, there are two parts to
install .
- Connect the infrared receiver ribbon cable.
- Install the filter.
- Place the hinges of the return air in openings A , then fasten the
grille with the locks on both sides .
- On models K 30 RCF and K 45 RCFA install the central grille by
twisting.
- Avoid distorsions of the frame caused by excessive traction;
the frame should be correctly centered in relation to the false
ceiling and it should especially ensure an airtight separation
between return air and supply air .
- The figure indicates the airtight packings, avoiding
A : the by-pass of air
B : discharge of treated air inside the false
ceiling.
- Check after installation that the space between frame and false
ceiling is less than 5 mm.
Latch of the grille
Packings
AIR INLET AND OUTLET
Return / Supply air grille
- Unpack the assembly with care. Fit the location snaps on the
corners of the frame.
- Position the frame on the unit and press on it to snap it in place.
This facilitates installation of the frame in its final position on the
unit. Then attach it with screws.
A
AA
A
A
1 3
K INST. MENU