LENGTH OF THE LINKINGS PIPES
COOLING SPECIFICATIONS
- The R22 charge depends on the length of the cooling linking
pipes.
Example:
- Installation of a réversible
K 30 RCF
with cooling pipes 10 m long:
-
Add + 282 g + 102 g = 384 g of R22 on site.
Maximum height of the cooling link
- The maximum permissible difference in height between the outdoor unit and the indoor unit is indicated in page11.
K 30 RCF K 45 RCF
0 grs : 1 -> 25m
1 m
- 51 grs
58 grs
26 m
2 m
- 34 grs
116 grs
27 m
3 m
- 17 grs
174 grs
28 m
4 m
232 grs
29 m
5 m
17 grs
290 grs
30 m
6 m
34 grs
348 grs
31 m
7 m
51 grs
406 grs
32 m
8 m
68 grs
464 grs
33 m
9 m
85 grs
522 grs
34 m
10 m
102 grs
580 grs
35 m
11 m
119 grs
638 grs
36 m
12 m
136 grs
696 grs
37 m
13 m
153 grs
754 grs
38 m
14 m
170 grs
812 grs
39 m
15 m
187 grs
870 grs
40 m
16 m
204 grs
928 grs
41 m
17 m
221 grs
986 grs
42 m
18 m
238 grs
1044 grs
43 m
19 m
255 grs
1102 grs
44 m
20 m
272 grs
1160 grs
45 m
21 m
289 grs
1218 grs
46 m
22 m
306 grs
1276 grs
47 m
23 m
323 grs
1334 grs
48 m
24 m
340 grs
1392 grs
49 m
25 m
357 grs
1450 grs
50 m
NOTE: for K30RCF to match with GC30RCC
NOTE: see RESTRICTOR INSTALLATION on page 18 when K30RCF to match with GC30RCC