17
Electrical Wiring
Code setting of wired controller
Function switches
Note: ON indicates short circuit; OFF indicates disconnection.
The difference between master and slave wired controller
Code
Switch status
Function description
Default setting
Remarks
SW1
ON
Auxiliary wired controller
OFF
OFF
Master wired controller
SW2
ON
Common wired controller
ON
OFF
New fan-only has refrigerating,
heating, and air supplying modes
SW3
ON
Display ambient temperature
OFF
OFF
Do not display ambient
temperature
SW4
ON
26ð lock disabled
ON
OFF
26ð lock enabled
SW5
ON
Collect ambient temperature of
wired controler
ON
OFF
Collect ambient temperature of
PCB
SW6
ON
Power failure memory disabled
OFF
OFF
Power failure memor enabled
SW7
ON
Temperature sensor 4k7 enabled
ON
Betewwn SW7
and SW8, one and
only one must be
ON for any given
period
OFF
Temperature sensor 4k7 disabled
SW8
ON
Temperature sensor 5k1 enabled
OFF
OFF
Temperature sensor 5k1 disabled
Topic
Master controller
Slave controller
Function
All function
ON/OFF, Mode, Fan speed, Temp, Swing function only.