16
Electrical Wiring
(B) Definition and description of SW03
Note 2:
•Set the address by code when connecting the centralized controller or gateway or charge
system.
•Address of centralized controller =communication a 0 or +64.
SW03_ 2=OFF, address of centralized controller =communication 0=communication
address
SW03_ 2=ON, address of centralized controller=communication 64 (applies when
centralized controller is used and there are more than 64 indoor units)
•To use with 0010451181A in use, it is required to use code for address setting. Set SW03_1=0N
and SW03_ 2=OFF; SW03_3, SW03_ 4, SW03_5, SW03_6, SW03_7 and SW03_ 8 are
address codes which are set according to actual address.
•Address setting function of wired controller for ultrathin card machine is disnabled.
SW03_1
Address
setting mode
[1]
Address setting mode
0
Automatic setting (default)
1
Code-set address
SW03_2
~
SW03_8
Code-set
indoor unit
address and
centralized
controller
address
(Note 2)
[2] [3] [4] [5] [6] [7] [8]
Address of
indoor unit
Address of
centralized
controller
0
0
0
0
0
0
0
0#
(Default)
0#
(Default)
0
0
0
0
0
0
1
1#
1#
0
0
0
0
0
1
0
2#
2#
…
…
…
…
…
…
…
…
…
0
1
1
1
1
1
1
63#
63#
1
0
0
0
0
0
0
0#
64#
1
0
0
0
0
0
1
1#
65#
1
0
0
0
0
1
0
2#
66#
…
…
…
…
…
…
…
…
…
1
1
1
1
1
1
1
63#
127#
SW08_1
WiFi Control
Mode Option
1
Single Control
0
Group Control
SW08_2
Passive contact,
OEM, total
heat exchanger
linkage
1
Generally--passive contact is disabled and there is no
linkage control in the unit with total heat exchanger.
0
Passive contact is enabled, there is linkage control in the
unit with total heat exchanger
SW08_3
Selection of
indoor unit
priority
1
General (default)
0
High priority (The target superheat degree of Tao in the
range of 10-43 will be reduced by 1 .)
SW08_4
90m high fall
between indoor
and outdoor units
1
General
0
High fall
(C) Definition and description of SW08
26°C Lock function Activation:
Default: Deactivated
Activation: Press "Health" button on remote controller 8 times in 5 seconds, and you hear 4
times beep, then activate the function.
Deactivation: Press "Health" button on remote controller 8 times in 5 seconds, and you hear 2
times beep, then deactivate the function.
Summary of Contents for AWSI-DDV007-N11
Page 3: ...1 Parts and Functions ...
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ......