Drainage pipe installation
According to the above table to calculate the total water flowrate for the confluence pipe selection.
For horizontal drainage pipe
(The following table is for reference)
PVC pipe
Reference value of inner
diameter of pipe (mm)
Allowable maximum water flowrate (l/h)
Remark
Slope 1/50
Slope 1/100
PVC25
20
39
27
For branch pipe
PVC32
25
70
50
PVC40
31
125
88
Could be used for confluence pipe
PVC50
40
247
175
PVC63
51
473
334
Attention: Adopt PVC40 or bigger pipe to be the main pipe.
For Vertical drainage pipe
(The following table is for reference)
PVC pipe
Reference value of inner
diameter of pipe (mm)
Allowable maximum water flowrate (l/h)
Remark
PVC25
20
220
For branch pipe
PVC32
25
410
PVC40
31
730
Could be used for confluence pipe
PVC50
40
1440
PVC63
51
2760
PVC75
67
5710
PVC90
77
8280
Attention: Adopt PVC40 or bigger pipe to be the main pipe.
6.2.3 Individual design of drainage pipe system
The drainage pipe of air conditioner shall be installed separately with other sewage pipe, rainwater pipe
and drainage pipe in building.
The drainage pipe of the indoor unit with water pump should be apart from the one without water pump.
6.2.4 Supporter gap of drainage pipe
In general, the supporter gap of the drainage pipe horizontal pipe and vertical pipe is respectively
1m~1.5m and 1.5m~2.0m.
Each vertical pipe shall be equipped with not less than two hangers.
Overlarge hanger gap for horizontal pipe shall create bending, thus leading to air block.
Too long distance
Gas bag
6.2.5 The horizontal pipe layout should avoid converse flow or bad flow
Drainage pipe
Water flow
Drainage pipe
Drainage pipe
Drain
tee
Drain
tee
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Drain
tee
105
Summary of Contents for AW-C AW-FFM036T-N11
Page 3: ...General Information Part 1 General Information 1 Model Lists 2 2 External Appearance 3 1...
Page 6: ...External Appearance 2 2 Outdoor Units Single fan outdoor unit Double fan outdoor unit 4...
Page 10: ...Dimensions Dimensions 8...
Page 11: ...Service Space Service Space 9...
Page 13: ...Wiring Diagrams Wiring Diagrams MCA3 12HRN1 Q MCA3 18HRN1 Q 11...
Page 17: ...Indoor Units Field Wiring 15...
Page 23: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000m m 21...
Page 24: ...Wiring Diagrams 4 Wiring Diagrams AW CFM024 N11 AW CFM036 N11 22...
Page 25: ...Indoor Units AW CFM036T N11 23...
Page 26: ...Wiring Diagrams AW CFM048 N11 24...
Page 31: ...Indoor Units 9 Field Wiring AW CFM012 N11 AW CFM018 N11 AW CFM024 N11 AW CFM036 N11 29...
Page 32: ...Field Wiring AW CFM024 N11 AW CFM036 N11 30...
Page 33: ...Indoor Units AW CFM036T N11 AW CFM048 N11 31...
Page 36: ...Features Max 750mm 34...
Page 39: ...Wiring Diagrams 4 Wiring Diagrams AW DFM018 N11 AW DFM018 N11 37...
Page 40: ...Wiring Diagrams AW DFM036 N11 AW DFM036T N11 38...
Page 41: ...Wiring Diagrams AW DFM048 N11 39...
Page 42: ...Wiring Diagrams AW DFM060 N11 40...
Page 49: ...Field Wiring 10 Field Wiring AW DFM018 N11 AW DFM024 N11 47...
Page 50: ...Field Wiring AW DFM036 N11 AW DFM036T N11 48...
Page 51: ...Field Wiring AW DFM048 N11 AW DFM060 N11 49...
Page 55: ...Service Space 3 Service Space 53...
Page 56: ...Wiring Diagram 4 Wiring Diagram AW FFM018 N11 AW FFM024 N11 54...
Page 57: ...Wiring Diagram AW FFM036T N11 AW FFM036T N11 55...
Page 58: ...Wiring Diagram AW FFM048 N11 AW FFM060 N11 56...
Page 63: ...Field Wiring 9 Field Wiring AW FFM018 N11 61...
Page 64: ...Field Wiring AW FFM024 N11 AW FFM036T N11 62...
Page 65: ...Field Wiring AW FFM036 N11 AW FFM048 N11 AW FFM060 N11 63...
Page 73: ...Wiring Diagrams 4 Wiring Diagrams AW YFFA012 H11 AW YFFA018 H11 AW YFFA012 H11 71...
Page 74: ...Wiring Diagrams AW YFFA024 H11 72...
Page 75: ...Wiring Diagrams AW YFFA036 H11 73...
Page 76: ...Wiring Diagrams AW YFFA036 H13 AW YFFA048 H13 74...
Page 77: ...Wiring Diagrams AW YFFA060 H13 75...
Page 126: ...Troubleshooting f Refrigerant Leakage Detection 124...