Vacuum Drying and Leakage Checking
shall cause shutdown of unit. When this situation happens, the normal startup only can be recovered by
turning down power supply and eliminating accumulated water.
Note:
Drain plug at the main water-containing plate is used for eliminating accumulated water in
water-containing plate when maintaining air conditioner fault. During normal operation, the plug shall be
filled in to prevent leakage.
6.4 Insulation work of drainage pipe
Refer the introduction to the insulation engineering parts.
7. Vacuum Drying and Leakage Checking
7.1 Purpose of vacuum drying
Eliminating moisture in system to prevent the phenomena of ice-blockage and copper oxidation.
Ice-blockage shall cause abnormal operation of system, while copper oxide shall damage compressor.
Eliminating the non-condensable gas (air) in system to prevent the components oxidizing, pressure
fluctuation and bad heat exchange during the operation of system.
7.2 Selection of vacuum pump
The ultimate vacuum degree of vacuum pump shall be -756mmHg or above.
Precision of vacuum pump shall reach 0.02mmHg or above.
7.3 Operation procedure for vacuum drying
Due to different construction environment, two kinds of vacuum drying ways could be chosen, namely
ordinary vacuum drying and special vacuum drying.
7.3.1 Ordinary vacuum drying
1. When conduct first vacuum drying, connect pressure gauge to the infusing mouth of gas pipe and liquid
pipe, and keep vacuum pump running for 1hour (vacuum degree of vacuum pump shall be reached
-755mmHg).
2 If the vacuum degree of vacuum pump could not reach -755mmHg after 1 hour of drying, it indicates
that there is moisture or leakage in pipeline system and need to go on with drying for half an hour.
3 If the vacuum degree of vacuum pump still could not reach -755mmHg after 1.5 hours of drying, check
whether there is leakage source.
4 Leakage test: After the vacuum degree reaches -755mmHg, stop vacuum drying and keep the pressure
for 1 hour. If the indicator of vacuum gauge does not go up, it is qualified. If going up, it indicates that
there is moisture or leak source.
7.3.2 Special vacuum drying
The special vacuum drying method shall be adopted when:
1.
Finding moisture during flushing refrigerant pipe.
2.
Conducting construction on rainy day, because rain water might penetrated into pipeline.
3.
Construction period is long, and rain water might penetrated into pipeline.
4.
Rain water might penetrate into pipeline during construction.
Procedures of special vacuum drying are as follows:
1.
Vacuum drying for 1 hour.
2.
Vacuum damage, filling nitrogen to reach 0.5Kgf/cm2 .
Because nitrogen is dry gas, vacuum damage could achieve the effect of vacuum drying, but this
method could not achieve drying thoroughly when there is too much moisture. Therefore, special
attention shall be drawn to prevent the entering of water and the formation of condensate water.
3.
Vacuum drying again for half an hour.
If the pressure reached -755mmHg, start to pressure leakage test. If it can not reached the value,
repeat vacuum damage and vacuum drying again for 1 hour.
108
Summary of Contents for AW-C AW-FFM036T-N11
Page 3: ...General Information Part 1 General Information 1 Model Lists 2 2 External Appearance 3 1...
Page 6: ...External Appearance 2 2 Outdoor Units Single fan outdoor unit Double fan outdoor unit 4...
Page 10: ...Dimensions Dimensions 8...
Page 11: ...Service Space Service Space 9...
Page 13: ...Wiring Diagrams Wiring Diagrams MCA3 12HRN1 Q MCA3 18HRN1 Q 11...
Page 17: ...Indoor Units Field Wiring 15...
Page 23: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000m m 21...
Page 24: ...Wiring Diagrams 4 Wiring Diagrams AW CFM024 N11 AW CFM036 N11 22...
Page 25: ...Indoor Units AW CFM036T N11 23...
Page 26: ...Wiring Diagrams AW CFM048 N11 24...
Page 31: ...Indoor Units 9 Field Wiring AW CFM012 N11 AW CFM018 N11 AW CFM024 N11 AW CFM036 N11 29...
Page 32: ...Field Wiring AW CFM024 N11 AW CFM036 N11 30...
Page 33: ...Indoor Units AW CFM036T N11 AW CFM048 N11 31...
Page 36: ...Features Max 750mm 34...
Page 39: ...Wiring Diagrams 4 Wiring Diagrams AW DFM018 N11 AW DFM018 N11 37...
Page 40: ...Wiring Diagrams AW DFM036 N11 AW DFM036T N11 38...
Page 41: ...Wiring Diagrams AW DFM048 N11 39...
Page 42: ...Wiring Diagrams AW DFM060 N11 40...
Page 49: ...Field Wiring 10 Field Wiring AW DFM018 N11 AW DFM024 N11 47...
Page 50: ...Field Wiring AW DFM036 N11 AW DFM036T N11 48...
Page 51: ...Field Wiring AW DFM048 N11 AW DFM060 N11 49...
Page 55: ...Service Space 3 Service Space 53...
Page 56: ...Wiring Diagram 4 Wiring Diagram AW FFM018 N11 AW FFM024 N11 54...
Page 57: ...Wiring Diagram AW FFM036T N11 AW FFM036T N11 55...
Page 58: ...Wiring Diagram AW FFM048 N11 AW FFM060 N11 56...
Page 63: ...Field Wiring 9 Field Wiring AW FFM018 N11 61...
Page 64: ...Field Wiring AW FFM024 N11 AW FFM036T N11 62...
Page 65: ...Field Wiring AW FFM036 N11 AW FFM048 N11 AW FFM060 N11 63...
Page 73: ...Wiring Diagrams 4 Wiring Diagrams AW YFFA012 H11 AW YFFA018 H11 AW YFFA012 H11 71...
Page 74: ...Wiring Diagrams AW YFFA024 H11 72...
Page 75: ...Wiring Diagrams AW YFFA036 H11 73...
Page 76: ...Wiring Diagrams AW YFFA036 H13 AW YFFA048 H13 74...
Page 77: ...Wiring Diagrams AW YFFA060 H13 75...
Page 126: ...Troubleshooting f Refrigerant Leakage Detection 124...