Drainage pipe installation
5.2.11 Set the supporter for the pipe.
5.2.12 Locate the pipe and fix it by supporter
For horizontal refrigerant pipe, the distance between supporters should not be exceed 1m.
For vertical refrigerant pipe, the distance between supporters should not be exceed 1.5m.
5.2.13 Connect the pipe to indoor unit and outdoor unit by using two spanners.
Be sure to use two spanners and proper torque to fasten the nut, too large torque will damage the
bellmouthing, and too small torque may cause leakage. Refer the following table for different pipe
connection.
Pipe Diameter
Torque
Sketch map
(kgf.cm)
(N.cm)
1/4" (6.35)
144~176
1420~1720
3/8" (9.52)
333~407
3270~3990
1/2" (12.7)
504~616
4950~6030
5/8" (15.9)
630~770
6180~7540
3/4" (19)
990~1210
9270~11860
6. Drainage pipe installation
Install the drainage pipe as shown below and take measures against condensation. Improperly installation
could lead to leakage and eventually wet furniture and belongings.
6.1 Installation principle
Ensure at least 1/100 slope of the drainage pipe
Adopt suitable pipe diameter
Adopt nearby condensate water discharge
6.2 Key points of drainage water pipe installation
6.2.1 Considering the pipeline route and elevation
Before installing condensate water pipeline, determine its route and elevation to avoid intersection with
other pipelines and ensure slope is straight.
6.2.2 Drainage pipe selection
The drainage pipe diameter shall not small than the drain hose of indoor unit
According to the water flowrate and drainage pipe slope to choose the suitable pipe, the water flowrate
is decided by the capacity of indoor unit.
Relationship between water flowrate and capacity of indoor unit
Capacity (x1000Btu)
Water flowrate (l/h)
12
2.4
18
4
24
6
30
7
36
8
42
10
48
12
60
14
104
Summary of Contents for AW-C AW-FFM036T-N11
Page 3: ...General Information Part 1 General Information 1 Model Lists 2 2 External Appearance 3 1...
Page 6: ...External Appearance 2 2 Outdoor Units Single fan outdoor unit Double fan outdoor unit 4...
Page 10: ...Dimensions Dimensions 8...
Page 11: ...Service Space Service Space 9...
Page 13: ...Wiring Diagrams Wiring Diagrams MCA3 12HRN1 Q MCA3 18HRN1 Q 11...
Page 17: ...Indoor Units Field Wiring 15...
Page 23: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000m m 21...
Page 24: ...Wiring Diagrams 4 Wiring Diagrams AW CFM024 N11 AW CFM036 N11 22...
Page 25: ...Indoor Units AW CFM036T N11 23...
Page 26: ...Wiring Diagrams AW CFM048 N11 24...
Page 31: ...Indoor Units 9 Field Wiring AW CFM012 N11 AW CFM018 N11 AW CFM024 N11 AW CFM036 N11 29...
Page 32: ...Field Wiring AW CFM024 N11 AW CFM036 N11 30...
Page 33: ...Indoor Units AW CFM036T N11 AW CFM048 N11 31...
Page 36: ...Features Max 750mm 34...
Page 39: ...Wiring Diagrams 4 Wiring Diagrams AW DFM018 N11 AW DFM018 N11 37...
Page 40: ...Wiring Diagrams AW DFM036 N11 AW DFM036T N11 38...
Page 41: ...Wiring Diagrams AW DFM048 N11 39...
Page 42: ...Wiring Diagrams AW DFM060 N11 40...
Page 49: ...Field Wiring 10 Field Wiring AW DFM018 N11 AW DFM024 N11 47...
Page 50: ...Field Wiring AW DFM036 N11 AW DFM036T N11 48...
Page 51: ...Field Wiring AW DFM048 N11 AW DFM060 N11 49...
Page 55: ...Service Space 3 Service Space 53...
Page 56: ...Wiring Diagram 4 Wiring Diagram AW FFM018 N11 AW FFM024 N11 54...
Page 57: ...Wiring Diagram AW FFM036T N11 AW FFM036T N11 55...
Page 58: ...Wiring Diagram AW FFM048 N11 AW FFM060 N11 56...
Page 63: ...Field Wiring 9 Field Wiring AW FFM018 N11 61...
Page 64: ...Field Wiring AW FFM024 N11 AW FFM036T N11 62...
Page 65: ...Field Wiring AW FFM036 N11 AW FFM048 N11 AW FFM060 N11 63...
Page 73: ...Wiring Diagrams 4 Wiring Diagrams AW YFFA012 H11 AW YFFA018 H11 AW YFFA012 H11 71...
Page 74: ...Wiring Diagrams AW YFFA024 H11 72...
Page 75: ...Wiring Diagrams AW YFFA036 H11 73...
Page 76: ...Wiring Diagrams AW YFFA036 H13 AW YFFA048 H13 74...
Page 77: ...Wiring Diagrams AW YFFA060 H13 75...
Page 126: ...Troubleshooting f Refrigerant Leakage Detection 124...