Electrical Control Function
Electrical Control System
115
2) When the follow-me function is available, the PCB will not respond according to the setting temperature
from follow-me signal every 3 minutes.
3) The PCB will take action to the mode change information from remote controller signal, and the
follow-me function will be turned off. (if the wired remote controller does not initiate follow me function).
4) When the unit is running with follow-
me function, if the PCB doesn’t receive any signal from remote
controller for 7 minutes or pressing FOLLOW ME button again, the follow-me function will be turned off
automatically, and the temperature collection function of room temperature sensor will be available, the
PCB will control the unit according to the room temperature detected from its own room temperature
sensor and setting temperature.
5) When the indoor PCB receives the follow-me signal from wired remote controller, the control is the
same as that from wireless remote controller, but buzzer will not respond. When the PCB receives
turning-off follow-me signal from wired remote controller, the unit will quit follow-me function at once.
The follow-me function controlled by wired remote controller prevails that by wireless remote controller.
1.3.13 8
℃
Heating(optional)
In heating operation, the preset temperature of the air conditioner can be as lower as 8
℃
, which keeps the
room temperature steady at 8
℃
and prevents household things freezing when the house is unoccupied for
a long time in severe cold weather.
1.3.14 Mode conflict
The indoor units cannot work cooling mode and heating at same time.
Heating mode has a priority.
(1) Definition
Cooling mode
Heating Mode
Fan
Off
Cooling mode
No
Yes
No
No
Heating Mode
Yes
No
Yes
No
Fan
No
Yes
No
No
Off
No
No
No
No
No: No mode conflict;
Yes: Mode conflict
(2) Unit action
In case of one Indoor unit working in cooling mode or fan mode, and another indoor unit is set to heating
mode, the indoor unit working in cooling mode or fan mode will change to off. The outdoor unit will
change to heating mode after compressor stop 3 minutes. .
In case of one Indoor unit working in heating mode, and another indoor unit is set to cooling mode or fan
mode, the indoor unit setting to cooling mode or fan mode will change to stand by. The outdoor unit will
continue working in heating mode.
If heating mode stops (not including the indoor unit in heating mode reaching the set temperature), 3
minutes after the outdoor unit restarts and works in cooling mode or fan-only mode.
1.3.15 Point Check Function
There is a check switch in outdoor PCB.
Press the switch SW1 to check the states of unit when the unit is running.
Summary of Contents for 7SP091170
Page 16: ...Indoor Units 14 Indoor Units Part 2 Indoor Units HKD Type 15 HND Type 28 Light Commercial 41...
Page 28: ...Exploded View and Spare Part list 26 Indoor Units 4 7 Exploded view of model AWSI HKD024 N11...
Page 33: ...Dimensions Indoor Units 31 For AWSI HND012 N11 For AWSI HND018 N11 For AWSI HND024 N11...
Page 37: ...Exploded View and Spare Part list Indoor Units 35 4 3 Exploded view of model AWSI HND012 N11...
Page 39: ...Exploded View and Spare Part list Indoor Units 37 4 5 Exploded view of model AWSI HND018 N11...
Page 41: ...Exploded View and Spare Part list Indoor Units 39 4 7 Exploded view of model AWSI HND024 N11...
Page 45: ...Features Indoor Units 43 Dimension 75mm Fresh Air...
Page 50: ...Dimensions 48 Indoor Units 2 Dimensions 2 1 Four way cassette type compact 270...
Page 52: ...Dimensions 50 Indoor Units 2 3 Console...
Page 54: ...Service Space 52 Indoor Units 3 3 Console...
Page 57: ...Wiring Diagrams Indoor Units 55 4 5 AWSI DCD012 N11...
Page 58: ...Wiring Diagrams 56 Indoor Units 4 6 Model AWSI DID012 N11...
Page 59: ...Wiring Diagrams Indoor Units 57 4 7 AWSI XAD012 N11 4 8 Model AWSI XBD012 N11...
Page 72: ...Exploded View and Spare Part list 70 Indoor Units 5 13 Exploded view of model AWSI DID012 N11...
Page 74: ...Exploded View and Spare Part list 72 Indoor Units 5 15 Exploded view of model AWSI XBD009X N11...
Page 87: ...Wiring Diagrams Outdoor Units 85 4 Wiring Diagrams 4 1 AWAU YCZ218 H11 4 2 AWAU YCZ327 H11...
Page 88: ...Wiring Diagrams 86 Outdoor Units 4 3 AWAU YCZ430 H11...
Page 89: ...Wiring Diagrams Outdoor Units 87 AWAU YCZ542 H11 7SP091173...
Page 151: ...Electrical Control System 149 SERVICE MANUAL Multi Splits Series...